Complete Pre-Installation Checks; Install Indoor Unit - Carrier 40KMC Installation Instructions Manual

In-ceiling cassette duct-free split system
Hide thumbs Also See for 40KMC:
Table of Contents

Advertisement

INSTALLATION
Complete Pre-installation Checks
1. Unpack Unit - Store the indoor and outdoor units in the
original packaging until it is moved to the final site for in-
stallation.
When unpacking indoor unit, be careful not to
lift unit by condensate drain discharge pipe or by refrigerant
connections.
. Inspect Shipment - Upon receipt of shipment, check the
indoor and outdoor units for damage. If there is any dam-
age,
forward
claim
papers
directly
to the transportation
company. Manufacturer is not responsible for damage in-
curred in transit.
3. Inspect
Parts
Supplied
With
Units
— Check
all items
against parts list (see page 4). If any items are missing, noti-
fy your distributor or Carrier office.
To prevent loss or damage, leave all parts in original packages until
installation.
Consider System Requirements
1. Consult local building codes and NEC for special instaila-
tion requirements.
. When deciding the location of the indoor and outdoor units,
ensure that the piping run does not exceed the allowed dis-
tances listed in Table 3.
3. Make sure the indoor and outdoor units are easily accessible
to electrical power.
4. Allow sufficient clearances for airflow, wiring, refrigerant
piping, and servicing the unit. See Fig. 2 and Fig. 3.
5. Condensate piping can be directed through the inside wail
to an approved drain or straight outside.
INSTALL INDOOR UNIT
Plan the installation carefully before you begin.
1. Select indoor unit location.
a. A location that can bear the weight of the unit.
b. Install the unit a centrally as possible in the room.
c. Choose a location that does not obstruct air circulation.
NOTE:
A maximum of two air outlets can be restricted at one
time.
See Fig. 6. The Air Supply Outlet Obstruction accessory
kit can be used to obstruct air outlets.
t
'
'
'
it
¥
i
q
\
,
'
i
s
¢
"
¢
Max. 2 louvers closed
'
'
it
1
'
i
x
'
4
A07184
Fig. 6 - Air Outlet Obstruction
d. Choose a location that is easily accessible for service
and maintenance.
e. Do not install indoor units near a direct source of heat
such as direct sunlight or heating appliance.
f. Do not install units too close to humid conditions.
2. Mounting Indoor Unit
NOTE:
If the mounting location is in a plaster board ceiling,
the maximum dimensions of the unit housing cutout must not
exceed 2 ft, 2 in. (0.66 mm)
square for the 40KMC018
units
and 2 ft. 11 in. (0.66 mm) square for the 40KMC024-036 and
40KMQ018-036 units.
NOTE:
The unit is in two sections:
The unit and the grille.
a. Use the factory supplied cardboard template as a guide
to mark the position of the hangers, refrigerant lines and
condensate drain pipes, power supply cables and remote
control cables.
See Fig. 1 for dimensions.
b. Depending on the type of ceiling, fix the threaded
hangers as shown in Fig. 7 and Fig. 8.
4
|
C
—©®
J
@
=—__
@
©D-——— ©
1D
®
@ Nut
© Washer
@
Washers
@
Threaded hangers
@® Threaded hangers
Washer
@
Wooden frame
@® Nut
®
Nut
Nut
A07186
Fig. 7 - Attaching Hangers to Ceiling
é
|—_}*
Threaded hangers
L
a
"T bar
La"
be removed)
ale
AO7187
1
Fig. 8 - Threaded Hangers and "T" Bar
c. Insert the washers as shown in Fig. 7 and Fig. 8.
d. Remove the "T"bar in ceiling to facilitate installation.
See Fig. 8. If the "T" bar cannot be removed from the
ceiling, the unit may have to be tilted as shown in Fig.
9,
Threaded Hangers
Threaded Hangers
x,
LLe
|
te"
&
S|
|
x
T-Bar
T-Bar
Supension Brackets
Supension Brackets
A07I88
Fig. 9 - Positioning Unit in Ceiling
e. If Fresh Air Intake or Conditioning an Adjacent Room
is required, perform the modification required to the unit
at this point. Refer to the Installation Options section
for additional details.