Carrier WEATHERMAKER 48J Started Manual page 33

Single package large rooftop units with comfortlink ti version 5.x controls sizes (020-060)
Table of Contents

Advertisement

Table 42 -- Operating Modes Display Table
ITEM
SYS.M
HVAC
CTRL
MODE
OCC
T.OVR
DCV
SA.R
DMD.L
T.C.ST
IAQ.P
LINK
LOCK
H.NUM
EXPANSION
ascii string
ascii string
ascii string
RANGE
CCN POINT
n/a
n/a
n/a
MODES CONTROLLING
UNIT
Currently Occupied
ON/OFF
Timed Override in Effect
ON/OFF
DCV Resetting Min Pos
ON/OFF
Supply Air Reset
ON/OFF
Demand Limit in Effect
ON/OFF
Temp.Compensated
Start
ON/OFF
IAQ Pre-Occ Purge Active
ON/OFF
Linkage Active -- CCN
ON/OFF
Mech.Cooling
Locked Out
ON/OFF
HVAC Mode Numerical Form
number
MODEOCCP
MODETOVR
MODEADCV
MODESARS
MODEDMLT
MODETCST
MODEIQPG
MODELINK
MODELOCK
MODEHVAC
Supply Air Reset (SA.R) -- This variable displays if the sup-
ply air reset is currently active. This applies to cooling only.
Demand
Limit in Effect (DMD.L)
--
This variable
displays
if the mechanical
cooling capacity is currently being limited or
reduced by an outside third party.
Temperature
Compensated
Start (T.CST)
--
This variable
displays
if Heating
or Cooling
has been initiated
before the
occupied period to pre-condition
the space.
IAQ Pre-Occupanc¥
Purge Active (IAQ.P)
--
This variable
displays
if the economizer
is open and the fan is on to pre-
ventilate the building before occupancy.
Linkage
Active CCN (LINK)
--
This variable
displays
if a
linkage
master in a zoning system has established
"linkage"
with this air source (rooftop).
Mechanical
Cooling
Locked Out (LOCK)
--
This variable
displays if mechanical
cooling is currently being locked due to
low outside air teruperature.
HVAC Mode Numerical
Forru (H.NUM)
-- This is a numer-
ical representation
of the HVAC modes which may be read via
a point read.
SYSTEM
MODES
(Operating
Modes--cSYS.M)
Svsteru Mode Off--
When the system mode is OFF, all out-
puts are to be shut down and no machine
control is possible.
The following
list displays
the text assigned
to the System
Mode when
in the OFF mode and the conditions
that may
cause this mode are checked in the following hierarchal
order:
1. Wake up thner on a power reset.
("Initializing
Systeru ...")
2. Systeru in the process of shutting down compressors
and
waiting for thneguards
to expire.
("Shutting
Down...")
3. Factory
shut down
(internal
factory
control
level
--
SHUTDOWN).
("Factory
Shut Down")
4. Unit stop (software
application
level variable that acts as
a hard shut down -- Service
Test-+STOP).
("Local Machine
Stop")
5. Fire shut down (traumatic
fire shutdown
condition based
on the Fire Shutdown Input-
Inputs'--+FIRE-+FSD).
("Fire-Shutdown
Mode")
6. Eruergency
stop, which is forced over the CCN through
the Eruergency
Stop Variable (EMSTOP).
("CCN Eruergency
Stop")
7. Startup delay.
("Startup delay = 0-900 secs")
8. Service test ending transition timer.
("Service Test Ending")
9. Unexplained
internal software failure.
("Internal Failure")
System
Mode Test -- When the systeru mode is Test, the con-
trol is lhnited to the Test mode and is controllable
via the local
displays
(scrolling
marquee
and
Navigator
TM
display)
or
through
the factory
service
test control.
The
System
Test
modes are Factory Test Enabled and Service Test Enabled. See
the Service Test Mode section for details on test control in this
mode.
1. Factory Test mode
("Factory
test enabled")
2. Service Test mode
("Service test enabled")
System
Mode Run -- When the systeru mode is Run, the soft-
ware application
in the control is free to run the HVAC control
routines by which cooling, heating, IAQ, etc., is possible. There
are two possible text displays for this 1node, one is norrual run
mode and the other occurs if one of the following
fire-sruoke
modes is present: sruoke purge, pressurization
or evacuation.
1. Norrual run thne state
("Unit Operation Enabled")
2. Fire-Sruoke
control mode
("Fire-Sruoke
Control")
HVAC MODES
(Operating
Mode-+HVAC)
-- The system
mode must be selected before the unit controls can select the
HVAC mode of the rooftop
unit. The selection
of an HVAC
mode is based on a hierarchal decision making process. Certain
overrides may interfere with this process and the norrual teru-
peramre/huruidity
control operation
of the unit. The decision
making process
that deterruines
the HVAC 1node is shown in
Fig. 4 and Appendix
D.
Each HVAC Mode is described
below. The HVAC mode
number is shown in parenthesis
after the mode.
HVAC Mode -- STARTING
UP (0) --
The unit
is transi-
tioning froru the OFF 1node to a different mode.
HVAC Mode-
DISABLED
(1) --
The unit is shut down
due to a software colmnand
disable through the scrolling mar-
quee, a CCN emergency
stop colrnnand, a service test end, or a
control-type
change delay.
HVAC Mode -- SHUTTING
DOWN
(2) -- The unit is tran-
sitioning froru a mode to the OFF mode.
HVAC Mode -- SOFTSTOP
REQUEST
(3) --
The unit is
off due to a soft stop request froru the control.
HVAC Mode -- REM SW.DISABLE
(4) --
The unit is off
due to the reruote switch.
HVAC Mode -- FAN STATUS FAIL (5) -- The unit is off
due to failure of the fan status switch.
HVAC Mode -- STATIC PRESSURE
FAIL (6) -- The unit is
off due to failure of the static pressure sensor.
HVAC Mode -- COMRSTUCK
ON (7) --
The unit is shut
down because
there is an indication
that a compressor
is run-
ning even though it has been colrnnanded
off.
HVAC Mode -- OFF (8) -- The unit is off and no operating
modes are active.
HVAC Mode -- TEST (9) -- The unit is in the self test mode
which is entered through the Service Test menu.
HVAC Mode -- TEMPERING
VENT (10) --
The
econo-
lnizer is at ruinhnuru
vent position but the supply-air
terupera-
ture has dropped
below the terupering
vent set point. Staged
gas heat is used to teruper the ventilation
air.
HVAC Mode -- TEMPERING
LOCOOL
(11) -- The econ-
omizer is at minimum
vent position but the combination
of the
outside-air
teruperamre
and
the economizer
position
has
dropped the supply-air
temperature
below the tempering
cool
set point. Staged gas heat is used to teruper the ventilation
air.
33

Hide quick links:

Advertisement

Table of Contents
loading