Carrier WEATHERMAKER 48J Started Manual page 68

Single package large rooftop units with comfortlink ti version 5.x controls sizes (020-060)
Table of Contents

Advertisement

ECONOMIZER
MINIMUM
DAMPER
POSITION
MINIMUM
IAQ
DAMPER
POSITION
lOO
5oo
/
/
AQ
AQ
DIFFERENTIAL
DIFFERENTIAL
LOW
(DAQ.L)
HIGH
(DAQ.H)
700
INSIDE/OUTSIDE
CO 2 DIFFERENTIAL
10O0
INSIDE CO 2 CONCENTRATION
s
Fig. 12 -- IAQ Control
Z
...
"6
Iii
<o
...................
;
:
:
P_{
{ ,I
!:
I/
ill
0 8_
,
;;;:
_at_y
;i - 0- - 0-0--(:
i
::
:;
;
: i
i
: BAQ B
:
:
::
{ :f
i
;
;
;
5
4
3
2
1
0
-1
-2
-3
-4
-5
DAQ.L!
InsidelOutside
002 Differential
i DAQ.H
NOTE: Calculating
the IAQ.M and EC.MN damper position based
on differential
IAQ measurement,
Based on the configuration
parameter
IAQREACT, the reaction to
damper positioning
based on differential
air quality ppm can be
adjusted,
IAQREACT = 1 to 5 (more responsive)
IAQREACT = 0 (linear)
IAQREACT = -1 to-5
(less responsive)
Fig. 13 -- IAQ Response Curve
• IQ.A.C = 4 (10K potentiometer minimum position) --
With a 10K linear potentiometer connected to TB5-6 and 7_
the economizer minimum position will be scaled linearly
from 0% (0 kilo-otnns) to ECMX
(10 kilo-otnns).
IAQ Analog Fan Config (Configuration---_IAQ---_AQ. _T---_
!Q.A.F) -- This configuration is used to configure the control
of the indoor fan. If this option is used then the IAQ sensor
must be in the space and not in the return duct. It has the fol-
lowing configurations:
• IQ.A.F = 0 (No Fan Start) -- IAQ demand will never
override normal indoor fan operation during occupied or
unoccupied period and turn it on.
• IQ.A.F = 1 (Fan On If Occupied) -- IAQ demand will
override normal indoor fan operation and turn it on (if
off) only during the occupied period (CV operation with
automatic fan).
• IQ.A.F
= 2 (Fan On Occupied/Unoccupied)
--
IAQ
demand will always override normal indoor fan operation
and turn it on (if off) during both the occupied and unoccu-
pied period. For IQ.A.F = 1 or 2_the fan will be turned on as
described above when DAQ is above the DAQ Fan On Set
Point ((bnfigurafion--+IAQ--+AQ.SP--+D.EON).
The fan
will be turned offwhen DAQ is below the DAQ Fan OffSet
Point ((bnfiguration--_IAQ--+AQ.SP--_D.EOF).
The con-
trol can also be set up to respond to a discrete IAQ input.
The discrete input is connected to TB5-6 and 7.
IAQ Discrete Input Config ((bn.figuration--+IAQ--+AQ.(T
--+IQ.L(3 -- This configuration is used to set the type of IAQ
sensor. The following are the options:
• IQ.LC = 0 (No Discrete Input) -- This is used to indicate
that no discrete input will be used and the standard IAQ
sensor input will be used.
• IQ.LC = 1 (IAQ Discrete Input) -- This will indicate
that the IAQ level (high or low) will be indicated by
the discrete input. When the IAQ level is low_ the
economizer minimum position will be Configuration--+
IA Q--+DC V.. C --+IAQ.M.
• IQ.LC = 2 (IAQ Discrete Input with Minimum Position
Override) -- This will indicate that the IAQ level (high
or low) will be indicated by the discrete input and the
economizer minimum position will be the IAQ override
position_ IQ. O.P (when high).
It is also necessary to configure how the fan operates when
using the IAQ discrete input.
IAQ Discrete Fan Config ((bn.figuration--+IAQ--+AQ.(T
--+IQ.LF) -- This is used to configure the operation of the
fan during an IAQ demand condition. It has the following
configurations:
• IQ.LF = 0 (No Fan Start) -- IAQ demand will never
override normal indoor fan operation during occupied or
unoccupied period and turn it on.
• IQ.LF = 1 (Fan On If Occupied) -- IAQ demand will
override normal indoor fan operation and turn it on (if
off) only during the occupied period (CV operation with
automatic fan).
• IQ.LF
= 2 (Fan On Occupied/Unoccupied)
--
IAQ
demand
will
always
override
normal
indoor
fan
operation and turn it on (if off) during both the occupied
and unoccupied period.
OAQ 4-20 mA Sensor Config (Con.figuration--+IAQ--+
AQ.(T_OQ.A.(3
-- This is used to configure the type of
outdoor sensor that will be used for OAQ levels. It has the fol-
lowing configuration options:
• OQ.A. C = 0 (No Sensor) -- No sensor will be used and
the internal software reference setting will be used.
• OQ.A.C = 1 (OAQ Sensor with DAQ) -- An outdoor
CO 2sensor will be used.
• OQ.A. C = 2 (4 to 20 mA Sensor without DAQ).
68