CONTROLS
SET POINT AND CONFIGURATION
LOG
Software
Version
MBB
CESR131343--
RCB
CESR131249--
ECB
CESR131249--
NAVI
CESR131227--
SCB
CESR131226--
CEM
CESR131174--
MARQ
CESR131171--
ITEM
EXPANSION
RANGE
DEFAULT
ENTRY
UNIT
UNIT CONFIGURATION
-_C.TYP
Machine Control Type
1 - 6 (multi-text strings)
4
-_CV.FN
Fan Mode (O=Auto, l=Cont)
0 - 1 (multi-text strings)
1
-_RM.CF
Remote Switch Config
0 -3 (multi-text strings)
0
-_CEM
CEM Module Installed
Yes/No
No
-_TCS.C
Temp.Cmp.Strt.Cool
Factr
0 - 60 min
0
-_TCS.H
Temp.Cmp.Strt.Heat
Factr
0 - 60 min
0
-_SFS.S
Fan Fail Shuts Down Unit
Yes/No
No
-_SFS.M
Fan Stat Monitoring Type
0 - 2 (multi-text strings)
0
-_VAV.S
VAV Unocc.Fan Retry Time
0 - 720 min
50
-_SlZE
Unit Size (20-60)
20 - 60
20
-_DP.XR
Disch.Press. Transducers
Yes/No
No
-_SP.XR
Suct. Pres. Trans. Type
0 -1 (multi-text strings)
0
-_RFG.T
Refrig: 0=R22 1=R410A
0 -1 (multi-text strings)
1
-_CND.T
Cnd HX Typ:O=RTPF I=MCHX
0 -1 (multi-text strings)
0
-_MAT.S
MAT Calc Config
0 - 2 (multi-text strings)
1
-_MAT.R
Reset MAT Table Entries?
Yes/No
No
-_MAT.D
MAT Outside Air Default
0-100%
20
-_ALTI
Altitude ........ in feet:
0 - 60000
0
-_DLAY
Startup Delay Time
0 - 900 sec
0
-_STAT
TSTAT_Both Heat and Cool
Yes/No
No
-_AUX.R
Auxiliary Relay Config
0 - 3
0
-_SENS
INPUT SENSOR CONFIG
-_SENS-_SPT.S
Space Temp Sensor
Enable/Disable
Disable
-_SENS-_SP.O.S
Space Temp Offset Sensor
Enable/Disable
Disable
-_SENS-_SP.O.R
Space Temp Offset Range
1 - 10
5
-_SENS-_RRH.S
Return Air RH Sensor
Enable/Disable
Disable
-_SENS-_FLT.S
Filter Stat.Sw.Enabled
?
Enable/Disable
Disable
COOL
COOLING CONFIGURATION
-_Z.GN
Capacity Threshold Adjst
-10 - 10
1
-_MC.LO
Compressor
Lockout Temp
-20 - 55 dF
40
-_C.FOD
Fan-Off Delay, Mech Cool
0 - 600 sec
60
-_MLV
Min. Load Valve? (HGBP)
Yes/No
No
-_M.M.
Motor Master Control
Yes/No
No
-_HPSP
Head Pressure Setpoint
80 - 150 d F
113
-_A I.EN
Enable Compressor
A1
Enable/Disable
Enable
-_A2.EN
Enable Compressor
A2
Enable/Disable
Enable
-_BI.EN
Enable Compressor
B1
Enable/Disable
Enable
-_B2.EN
Enable Compressor
B2
Enable/Disable
Enable
-_CS.A I
CSB A1 Feedback Alarm
Enable/Disable
Enable
-_CS.A2
CSB A2 Feedback Alarm
Enable/Disable
Enable
-_CS.BI
CSB B1 Feedback Alarm
Enable/Disable
Enable
-_CS.B2
CSB B2 Feedback Alarm
Enable/Disable
Enable
-_REV.R
Rev Rotation Verified ?
Yes/No
No
-_H.SST
Hi SST Alert DelayTime
5 - 30 min
10
EDT.R
EVARDISCHRGE
TEMP RESET
-_RS.CF
EDT Reset Configuration
0 - 3 (multi-text strings)
0
-_RTIO
Reset Ratio
0 - 10
2
-_LIMT
Reset Limit
0 - 20 ^F
10
-_RES.S
EDT 4-20 ma Reset Input
Enable/Disable
Disable
Manufacturer
reserves the right to discontinue, or change at any time, specifications
or designs without notice and without incurring obligations.
Catalog No. 04-53480050-01
Printed in U.S.A.
Form 48/50A-7T
Pg CL-1
5-08
Replaces:
48/50A-6T

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents