Condenser-Fan Adjustment; Four-Inch Filter Replacement; Power Failure; Refrigerant Charge - Carrier WEATHERMAKER 48J Started Manual

Single package large rooftop units with comfortlink ti version 5.x controls sizes (020-060)
Table of Contents

Advertisement

Condenser-Fan
Adjustment
NOTE:
Condenser
fans on size 060 MCHX
units
are not
adjustable.
1. Turn offunit power supply.
2. Remove fan guard.
3. Loosen fan hub setscrews.
4. Adjust fan height on shaft using a straightedge placed
across venturi and measure per Fig. 43.
5. Fill hub recess with perlnagum if rubber hubcap is missing.
6. Tighten setscrews and replace panel(s).
7. Turn on unit power.
Four-Inch Filter Replacement-
The 4-Inch Filter
Change
Mode variable is used to service the unit when 4-in.
filters are used. When
the filters need to be changed,
set
Service
rest-cE4.CH
= YES.
The unit will be placed
in
Service Test mode and the economizer
will move to the 40%
open position to facilitate removal of the 4-in. filters. After the
filters have been changed, set Service
Test---_E4. (2Tt = NO to
return the unit to normal operation.
Power Failure-
The economizer damper motor is a
spring return design. In event of power failure, dampers will
return to fully closed position until power is restored.
Refrigerant Charge
_
Amount
of refrigerant
charge is
listed on unit nameplate.
Refer to Carrier GTAC II; Module 5;
Charging,
Recovery,
Recycling,
and Reclamation
section for
charging methods and procedures.
Unit panels must be in place when unit is operating
during
charging procedure.
NOTE:
Do not use recycled
refrigerant
as it may contain
contaminants.
NO CHARGE-
Use standard
evacuating
techniques.
After
evacuating
system, weigh in the specified
amount of refriger-
ant from the unit nameplate.
LOW CHARGE
COOLING
All Units with Round Tube-Plate
Fin Condenser
Coils
--
Connect the gage set and a temperature-measuring
device to
the liquid line. Ensure that all condenser
fans are operating.
It
may be necessary
to block part of the coil on cold days to
ensure that condensing
pressures
are high enough
to turn on
the fans. Adjust the refrigerant
charge in each circuit to obtain
state point liquid subcooling
for specific models
as listed in
Table 123.
NOTE: Indoor-air cfm must be within normal operating range
of unit.
Table 123 - Round
Tube,
Plate Fin Unit Charge
UNIT
REFRIGERANT
SIZE
LIQUID
48/50
TYPE
SUBCOOLING
020, 025, 027,
030,035,040,
20 F _+ 2 F
AJ,AK,AW, A Y
R-22
050, 060
036
18F_+2F
041,051
15 F_+2 F
020,027, 040,
15 F _+ 2 F
050,060
A2,A3,A4,A5
R-410A
030,035
20 F _+2 F
025
12F_+2F
48/50A2_A3
_4_A5 Units with MCHX
Condenser
--
Due
to the compact,
all aluminum
design,
microchannel
heat
exchangers
will reduce refrigerant
charge and overall operating
weight.
As a result, charging
procedures
for MCHX
units
require more accurate measurement
techniques.
Charge should
be added in small increments.
Using cooling charging
charts
provided
(Fig. 44-50), add or remove refrigerant
until condi-
tions of the chart are met. As conditions
get close to the point
on the chart, add or remove charge in 1/4 Ib increments until
complete. Ensure that all fans are on and all compressors are
running when using charging charts.
To Use the Cooling Charging Chart -- Use the outdoor air
temperature, saturated suction temperature and saturated con-
densing temperature (available on the (_n_fortLink
TM
display),
and find the intersection point on the cooling charging chart. If
intersection point is above the line, carefully recover some of
the refrigerant. If intersection point is below the line, carefully
add refrigerant.
NOTE: Indoor-air cfm must be within normal operating range
of unit.
Thermostatic Expansion Valve (TXV)
-- Each circuit
has a TXV. The TXV is adjustable
and is factory set to maintain
8 to 12 ° F superheat leaving the evaporator
coil. The TXV con-
trols flow of liquid refrigerant to the evaporator coils. Adjusting
the TXV is not reconnnended.
Gas Valve Adjustment
NATURAL
GAS -- The 2-stage gas valve opens and closes
in response to the thermostat or limit control.
When power is supplied to valve terminals 3 and 4, the pilot
valve opens to the preset position. When power is supplied to
terminals 1 and 2, the main valve opens to its preset position.
The regular factory setting is stamped on the valve body
(3.5 in. wg).
To adjust regulator:
1. Set thermostat
at setting for no call for heat.
2. Switch main gas valve to OFF position.
3. Remove
l/s-in, pipe plug from manifold.
Install a water
manometer
pressure-measuring
device.
4. Switch main gas valve to ON position.
5. Set thermostat
at setting to call for heat (high fire).
6. Remove screw cap covering
regulator
adjustment
screw
(See Fig. 51).
7. Turn adjustment
screw clockwise
to increase pressure or
counterclockwise
to decrease pressure.
8. Once desired pressure is established,
set unit to no call for
heat (3.3-in. wg high fire).
9. Switch main gas valve to OFF position.
10. Remove
pressure-measuring
device
and replace
l/s-in.
pipe plug and screw cap.
11. Turn main gas valve to ON position
and check heating
operation.
UNIT SIZE
I DIMENSION "A" (in.)
020-035, 050
1.30 _+0.12
036-041,051,060
0.87 _+0.12
Fig. 43 -- Condenser-Fan Adjustment
(All Units Except Size 060 MCHX)
132

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents