HVAC Mode -- TEMPERING
HICOOL
(12) --
The econ-
omizer is at minimum
vent
position
but the combination
of the
outside-air
temperature
and
the economizer
position
has
dropped the supply-air
temperature
below the tempering
cool
set point. Staged gas heat is used to temper the ventilation
air.
HVAC Mode-
VENT
(13) --
This is a normal
operation
mode where no heating or cooling is required and outside air is
being delivered to the space to control IAQ levels.
HVAC Mode -- LOW COOL (14) -- This is a normal cool-
ing mode where a low cooling demand is required.
HVAC Mode -- HIGH COOL (15) -- This is a normal cool-
ing mode where a high cooling demand is required.
HVAC Mode -- LOW HEAT (16) -- The unit will be in low
heating demand mode using either gas or electric heat.
HVAC Mode -- HIGH HEAT (17) --
The unit will be in
high heating demand mode using either gas or electric heat.
HVAC Mode -- UNOCC.
FREE
COOL (18)
--
In
this
mode the unit will operate
in cooling but will be using the
economizer
for free cooling. Entering this mode will depend on
the stares of the outside air. The unit can be configured for out-
side air changeover,
differential
dry bulb changeover,
outside
air enthalpy changeover,
differential
enthalpy
changeover,
or a
custom arrangement
of enthalpy/dewpoint
and dry bulb. See
the Economizer
section for further details.
HVAC Mode -- FIRE SHUT DOWN
(19) --
The unit has
been stopped due to a fire shutdown
input (FSD) or two or
more of the fire control modes, purge, evacuation,
or pressur-
ization have been requested shnultaneously.
HVAC Mode -- PRESSURIZATION
(20) -- The unit is in
the special fire pressurization
mode where the supply fan is on,
the economizer
damper is open and the power exhaust fans are
off. This mode is started by the Fire Pressurization
(PRES) in-
put which can be found in the INPUT---)FIRE
sub-menu.
HVAC Mode-
EVACUATION
(21) --
The unit is in the
special Fire Evacuation
mode where the supply fan is off, the
economizer
damper is closed and the power exhaust fans are
on. This mode is started by the Fire Evacuation
(EVA()
input
which can be found in the INPUT---_FIRE
sub-menu.
HVAC Mode -- SMOKE
PURGE
(22) -- The unit is in the
special Fire Purge mode where the supply fan is on, the econo-
mizer damper is open and the power exhaust fans are on. This
mode is started by the Fire Evacuation
(PURG)
input which
can be found in the INPUT---_FIRE
sub-menu.
HVAC Mode -- DEHUMIDIFICATION
(23) -- The unit is
operating in Dehumidification mode.
HVAC Mode-
REHEAT (24) -- The unit is operating in
reheat mode.
Unit Configuration
Submenu
E The UNIT sub-
menu under the Configuration mode of the local display
contains general unit configuration items. The sub-menu which
contains these configurations is located at the local display un-
der Configuration--+UNIT. See Table 43.
Machine Control Type (C TYP) --
This configuration de-
fines the control type and control source responsible for select-
ing a cooling, heating, or vent mode and in determining the
method by which compressors are staged. The control types
are:
C TYP = 1 (VAV-RAT) and C TYP = 2 (VAV-SPT)
Both of these configurations
refer to standard
VAV opera-
tion. If the control
is occupied,
the supply
fan is run
continuously
and return-air
temperature
will be used in the
determination
of the selection of a cooling mode. VAV-SPT
differs from VAV-RAT only in that during the unoccupied
period, space temperature
will be used instead of return-air
temperature
to start the fan for 10 minutes to establish
an
accurate return-air temperature before the return-air temper-
amre is allowed to call out any mode.
• C TYP = 3 (TSTAT-MULTI)
This configuration will force the control to monitor the ther-
mostat inputs to make a determination of mode. Unlike
traditional 2-stage thermostat control, the unit is allowed to
use multiple stages of cooling control and perform VAV-
type operation. The control will be able to call out a LOW
COOL or a HIGH COOL mode and maintain a low or high
cool supply air set point.
• C. TYP = 4 (TSTAT-2 STG)
This configuration will force the control to monitor the ther-
mostat inputs to make a determination of mode and allow
only 2 stages of control for both heating and cooling.
• C. TYP = 5 (SPT-MULTI)
This configuration will force the control to monitor a space
temperature sensor to make a determination of mode.
Unlike traditional 2-stage space temperature control, the
unit is allowed to use multiple stages of cooling control and
perform VAV-type operation. The control will be able to call
out a LOW COOL or a HIGH COOL mode and maintain a
low or high cool supply air set point.
• C. TYP = 6 (SPT-2 STG)
This configuration will force the control to monitor the
space temperature sensor to make a determination of mode
and allow 2 stages of control for both heating and cooling.
FAN MODE (CV..FN) -- The Fan Mode configuration can be
used
for
machine
control
types
(Configuration--€
UNIT_CTYP)
3, 4, 5, and 6. The Fan Mode variable
establishes the operating sequence for the supply fan during
occupied periods. When set to 1 (Continuous), the fan will
operate continuously during occupied periods. When set to 0
(Automatic), the fan will run only during a heating or cooling
mode.
REMOTE
SWITCH CONFIG (RM.CF)
-- The remote switch
input is connected
to TB6 terminals
1 and 3. This switch can be
used for several remote control functions.
Please refer to the
Remote Control Switch Input section for details on its use and
operation.
CEM MODEL
INSTALLED
(CEM) -- This configuration
in-
structs the control to co_rnnunicate
with the controls expansion
module (CEM) over the Local Equipment Network (LEN) when
set to Yes. When the unit is configured
for certain sensors and
configurations,
this option will be set to Yes automatically.
The sensors
and configurations
that automatically
turn on
this board are:
Configuration--cUNIT-+SFS.M
=
1 (Supply
Fan
Stares
Switch Monitoring)
Configuration-+EDT.R-+RES.S
= Enable (4 to 20 mA Sup-
ply Air Reset Sensor Enable)
Configuration--+DMD.L
-+DM.L.S
=
1
(2
SWITCHES)
(Demand Limiting using 2 discrete switches)
Configuration-+DMD.L--cDM.LS
= 2 (4-20
MA CTRL)
(Demand Limiting using a 4 to 20 mA sensor)
(bnfiguration--)IAQ--)AQ.CF-clQ.LC=
1 (IAQ DISCRETE)
(IAQ discrete switch control)
(bnfiguration--clAQ---)AQ.
(T--clQ.L
C = 2 (IAQ DISC.OVR)
(IAQ discrete switch "override" control)
(bnfiguration--clAQ--cAQ.(T_OQ.A.C
= 1 (OAQ SENS-
DAQ) (Outdoor Air Quality Sensor)
(bnfiguration--clAQ--cAQ.(T_OQ.A.C
=
2
(4-20
NO
DAQ) (4 to 20 mA sensor, no DAQ)
Temperature
Compensated
Start Cooling Factor
(TCS.()
--
This factor is used in the equation of the Temperature
Compen-
sated Start Time Bias for cooling. Refer to the Temperature
35