Carrier WEATHERMAKER 48J Started Manual page 56

Single package large rooftop units with comfortlink ti version 5.x controls sizes (020-060)
Table of Contents

Advertisement

STAGE
Table 73 -- Staged Gas Heat Control Steps (Configuration_HEAT_
SG.CT_HT.ST=
4)
RELAY OUTPUT
Heat 1
MBBIRLY8
IGC1
OFF
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
Heat 2
MBB-RLY7
MGV1
OFF
OFF
ON
OFF
ON
ON
OFF
ON
OFF
OFF
ON
ON
CAPACITY
%
Heat 3
SCB-RLY1
IGC2
OFF
OFF
OFF
OFF
OFF
OFF
ON
ON
ON
ON
ON
ON
Heat 4
SCB-RLY2
MGV2
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
ON
ON
ON
Heat 5
SCB-RLY3
IGC3
OFF
OFF
OFF
ON
ON
ON
OFF
OFF
ON
ON
ON
ON
Heat 6
SCB-RLY4
MGV3
OFF
OFF
OFF
OFF
OFF
ON
OFF
OFF
OFF
OFF
OFF
ON
0
0
1
19
2
25
3
38
4
44
5
50
6
57
7
63
8
76
9
88
10
94
11
100
RELOCATE
SAT (Supply
Air Temperature)
SENSOR
FOR
HEATING
IN LINKAGE
APPLICATIONS
-- On CCN in-
stallations
employing
ComfortID
TM
terminals, the factory SAT
location must be changed to a new location downstream
of the
unit's heating
system.
The ComfortID
terminal controls read
the SAT value for their "proof-of-heat"
sequence
before termi-
nals open to Minhnum
Heating positions
during unit heating
sequence.
Determine
a location in the supply duct that will provide
a
fairly uniform airflow. Typically this would be a minimum
of
5 equivalent
duct diameters
downstream
of the unit. Also, care
should be taken to avoid placing the thermistor
within a direct
line-of-sight
of the heating element to avoid radiant effects.
Run a new two-wire
conductor
cable from the control box
through the low voltage conduit into the space inside the build-
ing and route the cable to the new sensor location.
Installing
a New Sensor -- A field-provided
duct-mount
tem-
perature
sensor
(Carrier
P/N
33ZCSENPAT
or equivalent
10 kilo-otnn
at 25 C NTC [negative temperature
coefficient]
sensor) is required. Install the sensor through the side wall of
the duct and secure.
Table 74 -- IGC LED Indicators
LED INDICATION
On
Off
1 Flash
2 Flashes
3 Flashes
4 Flashes
5 Flashes
6 Flashes
7 Flashes
8 Flashes
9 Flashes
NOTES:
ERROR CODE
Normal Operation
Hardware Failure
Fan On/Off Delay Modified
Limit Switch Fault
Fame Sense Fault
Five Consecutive
Limit Switch Faults
Ignition Lockout Fault
Ignition Switch Fault
Rollout Switch Fault
Internal Control Fault
Software Lockout
1. There is a 3-second pause between error code displays.
2. If more than one error code exists, all applicable
error codes
will be displayed in numerical sequence.
3. Error codes on the IGC will be lost if power to the unit is
interrupted.
Re-Using
the Factory
SAT Sensor
--
The factory sensor
is
attached to one of the supply fan housings.
Disconnect
the sen-
sor from the factory harness.
Drill a hole insert the sensor
through the duct wall and secure in place.
Attach the new conductor
cable to the sensor leads and ter-
minate in an appropriate
junction
box. Connect
the opposite
end inside the unit control box at the factory leads from MBB
J8 terminals
11 and 12 (PNK)
leads. Secure the unattached
PNK leads from the factory harness
to ensure no accidental
contact with other terminals inside the control box.
MORNING
WARM UP -- Morning
Warm Up is a period of
time that assists CCN linkage in opening up downstream
zone
dampers for the first heating cycle of a day.
The Morning
Warm Up Period is CCN linkage
mode "2"
and is relayed in the following conditions:
Temperature
Compensated
Start Mode is active AND Heat
Mode in effect AND LAT is warm
enough
or is to be
ignored due to placement.
The unit just went into occupied
mode and there has been
no cooling
mode yet and a heat cycle occurs or was in
progress when the unit went occupied.
In both cases, if and when the heat mode terminates,
a heat
cycle has occurred
and any subsequent
heat cycles will not be
treated as a morning warm up period.
TEMPERING
MODE -- In a vent or cooling mode, the roof-
top may encounter
a situation
where the economizer
at mini-
1hum position is sending cold outside air down the ductwork of
the building. Therefore,
it may be necessary
to bring heat on to
counter-effect
this low supply-air
temperature.
This is referred
to as the tempering
mode.
Setting up the System
-- The relevant set points for Temper-
ing are located at the local display under Setpoints:
ITEM
T.PRG
T.CL
T.V.OC
T.V.UN
CON
EXPANSION
RANGE
UNITS
POINT
Tempering
-20-80
dF
TEMPPURG
Purge SASP
Tempering
in
5-75
dF
TEMPCOOL
Cool SASP
Tempering Vent
-20-80
dF
TEMPVOCC
Occ SASP
Tempering Vent
-20-80
dF
TEMPVUNC
Unocc. SASP
DEFAULT
5O
5
65
5O
Operation
-- First, the unit must be in a vent mode, a low cool
mode, or a high cool HVAC mode to be considered
for a tem-
pering mode. Secondly, the tempering
mode is only allowed
when the rooftop is configured
for staged gas (Configuration
--_HEA T--_HT. CF=3 ).
If the control is configured for staged gas, the control is in a
vent, low cool, or high cool HVAC mode, and the rooftop con-
trol is in a situation
where the economizer
must maintain
a
minimum
position,
then the evaporator
discharge temperature
(EDT) will be monitored.
If the EDT falls below a particular
trip point then the tempering
mode may be called out:
HVAC mode = "Tempering
Vent"
56