Carrier WEATHERMAKER 48J Started Manual page 96

Single package large rooftop units with comfortlink ti version 5.x controls sizes (020-060)
Table of Contents

Advertisement

IMPORTANT: If thecompressor
starts, verify
that the
indoor and outdoor fans are operating properly.
IMPORTANT: If the CS is.always detecting current, then
verify that the compressor is on. If the compressor is on,
check the contactor and the relay on the MBB. If the com-
pressor is off and there is no current, verify CS wiring and
replace if necessary.
IMPORTANT:
Return to Normal
mode and observe com-
pressor operation
to verify that compressor
current sensor
is working and condenser
fans are energized after compres-
sor starts.
A051 (Circuit A. Compressor
1 Stuck On Failure)
A052 (Circuit A. Compressor
2 Stuck On Failure)
A055 (Circuit B. Compressor
1 Stuck On Failure)
A056 (Circuit B. Compressor
2 Stuck On Failure)
--
Alarm
codes 051, 052, 055, and 056 are for compressors
A1, A2, B1,
B2 respectively.
These alarms occur when the current sensor
(CS) detects current when the compressor
should be off. When
this occurs, the control turns offthe compressor
and logs a strike
for the respective
circuit. Use the scrolling marquee to reset the
alarm.
If the current sensor board reads ON while the compressor
relay has been colnmanded
OFF for a period of 4 continuous
seconds,
an alarm is generated.
These alarms are only moni-
tored for a period of 10 seconds after the compressor
relay has
been colnmanded
OFE This is done to facilitate a service tech-
nician forcing a relay to test a compressor.
In addition, ifa compressor
stuck failure occurs and the cur-
rent sensor board reports the compressor
and the request off,
certain diagnostics
will take place.
1. If any of the 4 compressors
are diagnosed
as stuck on and
the current sensor board is on and the request is off, the
control will request the supply fan which will automati-
cally start building airflow control. Condenser
fans will
also be COlrnnanded on to maintain normal head pressure.
2. Heating will be disabled while any one of the compres-
sors has this problem.
The possible causes are:
welded contactor
frozen compressor relay on MBB
To check out alarms 051,052,
055, and 056:
1. Place the unit in Service
Test mode. All compressors
should be off.
2. Verify that there is not 24 v at the contactor coil. If there is
24 v at the contactor, check relay on MBB and wiring.
3. Check for welded contactor.
4. Verify CS wiring.
5. Return to Normal
mode and observe compressor
opera-
tion to verify that compressor
current sensor is working
and condenser
fans are energized after compressor
starts.
T064 (Circuit A Saturated
Condensing
Thermistor
Failure)
T065 (Circuit B Saturated
Condensing
Thermistor
Failure)
--
Alert codes 064 and 065 are for circuits A and B, respectively.
This alert code is for 48/50AJ,AK,AW,
AY units only. These
alerts occur when the saturated condensing
temperatures
(Tem-
peratures-¢REET-cSCT.A
and SCT.B)
are outside the range
-40 to 240 F (-40 to 116 C). When this occurs, the control uses
the outdoor temperature
(OAT) to control the outdoor fans. The
control will default to control based on the OAT sensor and will
turn on OFC.B when the ambient is above 65 F and off when
the ambient is below 50 E
If the SCT and OAT sensors have all failed then the control
should turn on OFC.B when compressors are on.
The cause of the alert is usually
a faulty thermistor,
a
shorted or open thermistor
caused by a wiring error, or a loose
connection.
T072 (Evaporator
Discharge
Reset Sensor Failure)
--
If the
unit is configured to use the remote EDT 4 to 20 mA reset in-
put ((bnfiguration--cEDT.R--cRES.S)
and the sensor reading
is less than 2 mA then the alert will occur. When this occurs the
control will default to the internal
set points.
The sensor
is
connected
to the optional CEM module.
For this sensor to be
used,
the EDT
4 to 20 mA
reset
input
((bnfiguration
-+EDT.R-+RES.S)
must be set to "enabled."
T073 (Outside
Air Temperature
Thermistor
Failure)
-- This
alert occurs when the outside air temperature
sensor (Temper-
atures-+AIR.T_OAT)
is outside
the range -40
to 240 F
(-40
to
116
C).
Failure
of this
thermistor
(Tempera-
tures-+AIR.T_OAT)
will disable any elements of the control
which requires
its use. Economizer
control beyond
the vent
position and the calculation
of mixed-air
temperature
for the
sumZ algorithin will not be possible. This alert resets automati-
cally. The cause of the alert is usually
a faulty thermistor,
a
shorted or open thermistor
caused by a wiring error, or a loose
connection.
T074 (Space Temperature Thermistor Failure) --
This alert
occurs when the space temperature sensor (Temperatures
---)AIR.T--+SPT) is outside the range -40 to 240 F (-40 to
116 C). This alert will only occur if the unit is configured to use
a space temperature sensor. Configuration is done through
the Unit Control
Type (Configuration--_UNIT-+CTYP)
configuration.
Failure
of
this
thermistor
(Tempera-
tures--+AIR.T--+SPT) will disable any elements of the control
which requires its use. If the unit is configured for SPT 2 stage
or SPT multi-stage operation and the sensor fails, no cooling or
heating mode may be chosen. This alert resets automatically.
The cause of the alert is usually a faulty thermistor in the T55,
T56, or T58 device, a shorted or open thermistor caused by a
wiring error, or a loose connection.
T075 (Return Air Thermistor Failure) -- This alert occurs
when
the
remm
air
temperature
sensor
(Tempera-
tures--)AIR. T--cRAT) is outside the range -40 to 240 F (-40 to
116 C). The RAT is standard on all units and is located in the
return section near the auxiliary control box. This alert resets
automatically. The cause of the alert is usually a faulty ther-
mistor, a shorted or open thermistor caused by a wiring error, or
a loose connection.
Failure of this thermistor
(Temperatures--)AIR.T---_RAT)
will disable any elements
of the control which requires its use.
Elements of failure include:
the calculation
of mixed air temperature
for sumZ control
the selection of a mode for VAV units
economizer
differential
enthalpy or dry bulb control
return air temperature
supply air reset
T076 (Outside
Air Relative
Humidity
Sensor Failure)
--
This alert occurs when the outside
air humidity
sensor
(In-
puts--cREL.H_OA.RH)
has a reading less than 2 mA. Failure
of this sensor will disable any elements of the control which re-
quires its use including economizer
outdoor and differential
en-
thalpy control. The OA.RH sensor is located in the economizer
hood and is used for control of the economizer.
The sensor is a
loop powered
4 to 20 mA sensor. This alert resets automatical-
ly. The cause of the alert is usually a faulty sensor, a shorted or
open sensor caused by a wiring error, or a loose connection.
The unit must be configured
to use the sensor through the Out-
side
Air
RH
Sensor
((bnfiguration-cE(ON_ORH.S)
setting.
T078 (Return Air Relative Humidity
Sensor Failure)
--
This
alert
occurs
when
the
remm
air
humidity
sensor
(Inputs--cRELH---_RA.RH)
has a reading
less than 2 mA.
Failure of this sensor (Inputs--cREL.H--cRA.RH)
will disable
96