D E MODE SELECTION
PROCESS
The following
section is to be used in conjunction
with
Fig. 4 on page 34. To help determine why the unit controls are
in a certain mode, the progralmning
logic is provided
below.
The software
will proceed,
step by step, until
a mode
is
reached. If an "If" statement is true, then that mode will be en-
tered. The "Else" statement refers to other possible choices.
If the System Mode is OFF:
{ If the fire shut down input (Inputs'--cFIRE-cFSD)
is in "alarm":
HVAC mode:
("Fire
Shut Down
") OFF
Else
HVAC mode:
("Disabled
") OFF}
Else If: The rooftop is not in "factory test" and a fire
smoke-control
mode is "alarming":
{ If the pressurization
input (Inputs'--+FIRE--+PRES)
is in "alarm":
HVAC mode:
("Pressurization
")
Else If the evacuation input (Inputs-+FIRE-+EVAO
is in "alarm":
HVAC mode:
("Evacuation
")
Else If the smoke purge input (Inputs'--+FIRE--+PURG)
is in "alarm":
HVAC mode:
("Smoke
Purge
")}
Else If: Someone changed the machine's
control type (Configuration-+UNIr_:
TYP) during
run time, a 15 second delay is called out:
{
HVAC mode:
("Disabled
") OFF}
Else If: The System Mode is TEST:
{
HVAC mode:
("Test
")}
Else If: The "soft stop" colmnand
(Service Test-+S.STP)
is forced to YES:
{
HVAC mode:
("SoftStop
Request")}
Else If: The remote switch config (Configuration--+
UNIT-+RM.
CF)
2; "start/stop",
and the remote
input state (Inputs-+GEN.I-+REMT)=ON:
{
HVAC mode:
("Rein.
Sw. Disable")
OFF}
Else If: Configured
for static pressure control
(Configuration---_SP---_SR
CF
1, 2) and the static
pressure sensor (Pressures-+AIR.P--+SP)
fails:
{
HVAC mode:
("Static
Pres.Fail")
OFF}
Else If: Configured
for supply fan status monitoring
(Configuration-cUNIT--)SFS.M
1,2) and
configured to shut the unit down on fan status fail
((bnfiguration--+UNIT--+SFS.S
= YES)
{
HVAC mode:
("Fan
Status Fail ") OFF}
Else If: The unit is just waking up from a power reset
{
HVAC mode:
("Starting Up
") OFF}
Else If: A compressor
is diagnosed
as being "Stuck On"
{
HVAC mode:
("Comp.
Stuck On ")
Else
The control is free to select the normal heating/
cooling HVAC modes:
{
HVAC mode:
("Off
")
--
The unit is off and no operating modes are active.
HVAC mode:
("Tempering
Vent
")
--
The economizer
is at minimum
vent position but
the supply air temperature
has dropped below the
tempering
vent set point. Gas heat is used to
temper the ventilation
air.
HVAC mode:
("Tempering
LoCool")
--
The economizer
is at minflnum vent position but
the combination
of the outside-air
temperature
and
the economizer
position has dropped the supply-air
temperature
below the tempering
cool set point.
Gas heat is used to temper the ventilation
air.
HVAC mode:
("Tempering
HiCool")
--
The economizer
is at minimum
vent position but
the combination
of the outside air temperature
and
the economizer
position has dropped the supply air
temperature
below the tempering
cool set point.
Gas heat is used to temper the ventilation
air.
HVAC mode:
("Re-Heat")
--
The unit is operating in reheat mode.
HVAC mode:
("Dehumidification")
--
The unit is operating in dehumidification
mode.
HVAC mode:
("Vent
")
--
This is a normal operation mode where no heating
or cooling is required and outside air is being
delivered to the space to control IAQ levels.
HVAC mode:
("Low
Cool
")
--
This is a normal cooling mode when a low cooling
demand exists.
HVAC mode:
("High
Cool
")
--
This is a normal cooling mode when a high
cooling demand exists.
HVAC mode:
("Low Heat
")
--
This is a normal heating mode when a low
heating demand exists.
HVAC mode:
("High Heat
")
--
This is a normal heating mode when a high
heating demand exists.
HVAC mode:
("Unoee. Free Cool")
--
In this mode the unit will operate in cooling but
will be using the economizer
for free cooling.
Entering this mode will depend on the status of the
outside air. The unit can be configured
for outside
air changeover,
differential
dry bulb changeover,
outside air enthalpy changeover,
differential
enthalpy changeover,
or a custom arrangement
of enthalpy/dewpoint
and dry bulb. See the
Economizer
section for further details.}
NOTE: There is also a transitional
mode whereby the machine
may be waiting for relay timeguards
to expire before shutting
the machine completely
down:
HVAC mode:
("Shutting
Down
")