Table 48 -- Cool/Heat Set Point Offsets Configuration
ITEM
D.LV.T
L.H.ON
H.H.ON
L.H.OF
L.C.ON
H.C.ON
L.C.OF
C. T.LV
H. T.LV
C.T.TM
H.T.TM
EXPANSION
COOL/HEAT
SETPT. OFFSETS
Dmd Level
Lo Heat On
Dmd Level(+) Hi Heat On
Dmd Level(-) Lo Heat Off
Dmd Level
Lo Cool On
Dmd Level(+) Hi Cool On
Dmd Level(-) Lo Cool Off
Cool Trend Demand Level
Heat Trend Demand
Level
Cool Trend Time
Heat Trend Time
[
RANGE
1
UNITS
1
CCN POINT
J
DEFAULT
-1 -2
0.5 - 20.0
0.5- 2
-1 -2
0.5 - 20.0
0.5- 2
0.1 -5
0.1 -5
30 - 600
30 - 600
AF
AF
AF
AF
AF
AF
AF
AF
sec
see
DMDLHON
DMDHHON
DMDLHOFF
DMDLCON
DMDHCON
DMDLCOFF
CTRENDLV
HTRENDLV
CTRENDTM
HTRENDTM
1.5
0.5
1
1.5
0.5
1
0.1
0.1
120
120
Timeguards
-- In addition to the set points and offsets which
determine
the trip points for bringing on and bringing off cool
modes there is a timeguard
of 8 minutes which enforces a time
delay between the transitioning
from a low cool to a high cool
mode. There is a timeguard
of 5 minutes which enforces a thne
delay between the transitioning
from a heat mode to a cool
mode.
Sz_ply Air Set Point (_ntrol
--
Once the control has deter-
mined that a cooling
mode is in effect, the cooling
control
point
(Run
Status-+VIEW_(Z.C.P)
is calculated
and
is
based upon either Setpoints-cSA.HI
or Setpoints-cSA.LO,
depending
on whether
a high or a low cooling
mode is in
effect, respectively.
In addition,
if supply air reset is config-
ured, it will also be added to the cooling control point.
Refer to the SumZ Cooling Algorithm
section for a discus-
sion of how the A Series
(_n_fortLink
TM
controls
manage
supply-air temperature
and the staging of compressors
for these
control types.
Thermostat
Cool Mode
Selection
((2: TYP = 3 and
4) --
When a thermostat
type is selected, the decision making pro-
cess involved
in determining
the mode
is straightforward.
Upon energizing
the Y1 input only, the unit HVAC mode will
be LOW COOL. Upon the energizing
of both Y1 and Y2 in-
puts, the unit HVAC mode will be HIGH COOL. If just input
G is energized
the unit HVAC mode will be VENT
and the
supply fan will run.
Selecting
the C TYP = 3 (TSTAT - MULTI)
control type
will cause the control to do the following:
• The control will read the Configuration-+UNIT--+SIZE
configuration
parameter
to determine
the number
of
cooling stages and the pattern
for each stage.
An HVAC mode
equal to LOW
COOL
will cause
the
unit to select the Setpoints-cSA.LO
set point to control
to. An HVAC mode equal to HIGH COOL will cause the
unit to select the Setpoints-cSA.HI
set point to control
to. Supply air reset (if configured)
will be added to either
the low or high cool set point.
The control will utilize the SumZ cooling
algoritlnn
and
control cooling
to a supply
air set point.
See the section
for the SumZ Cooling
Algorithm
section for information
on controlling
to a supply
air set point
and compressor
staging.
Selecting
the C TYP = 4 (TSTAT - 2 STG) control type
means that only two stages of cooling will be used. On unit
sizes 020, 025 and 027 (with three compressors),
an HVAC
Mode of LOW COOL will energize
one compressor
in Cir-
cuit A; an HVAC Mode of HIGH
COOL
will energize
all
three compressors.
On unit sizes 030 and larger (with four
compressors)
an HVAC Mode of LOW COOL will energize
both compressors
in Circuit
A; an HVAC Mode of HIGH
COOL will energize
all four compressors.
Refer to the sec-
tion on Economizer
Integration
with Mechanical
Cooling
for more information.
2-Stage
Cooling
Control
Logic ((: TYP = 4 and 6) --
The
logic that stages mechanical
cooling for the TSTAT and SPT
2-Stage
cooling
control types differs from that of the multi-
stage control types. This section will explain how compressors
are staged and the thning involved for both the Low Cool and
High Cool HVAC Modes.
There are either three or four compressors divided among two
refrigeration circuits. Circuit A always contains two compressors
(Outputs_COOL-cA1
and A2). Circuit B has either one com-
pressor (Outputs_,COOL-+B1)
on size 020-027 units or two
compressors
(Outputs_COOL-cB1
and B2) on size 030-060
units. For 2-stage cooling control, regardless
of configuration,
there is no mmhnum
load valve (MLV) control. The decision as
to which compressor
should be mined on or offnext
is decided
by the compressor's
availability and the preferred staging order.
Either A1 or A2 may start first as there is a built-in lead/lag
logic on compressors
A1 and A2 every time the unit stages to 0
compressors.
Also, based on compressor
availability, it should
be noted that any compressor
may come on. For example, on a
3 compressor
unit,
if no compressors
are currently
on,
compressor
A2 is currently under a minimum
off compressor
timeguard,
and 2 compressors
are to be turned on, then com-
pressors A1 and B1 will be turned on hmnediately
instead of
A1 and A2.
Low (_ol
Vels'us High (_ol Mechanical
Staging
The num-
ber of compressors
to be requested
during a cooling mode are
divided into 2 groups by the control, HVAC mode = Lo Cool
and HVAC mode = Hi Cool.
If the economizer
is not able to provide free cooling (Run
Status-+ECON--+ACTV
= NO)
then the following
staging
occurs
• Lo Cool Mode mechanical
stages = 2
• Hi Cool Mode mechanical
stages = 3 (for 020 through 027
size units)
Hi Cool Mode mechanical
stages = 4 (for 030 through 060
size units)
If the economizer
is able to provide
free cooling (Run Sta-
tus--+ECON---)ACTV
= YES)
then the following
staging
occurs
1. If the economizer's
current position is less than (bnfigu-
ration-cE(DN-cEC.MX-
5 and mechanical
cooling
has not yet started for the current cool mode session then:
Lo Cool Mode mechanical
stages = 0
Hi Cool Mode mechanical
stages = 0
2. During the first 2.5 minutes of a low or high cool mode
where the economizer
position is greater than (bnfigura-
tion --¢E(DN-cEC.MX-
5% and mechanical
cooling
has not yet started:
Lo Cool Mode mechanical
stages = 0
Hi Cool Mode mechanical
stages = 0
3. If the economizer
position is greater than (bnfiguration
--+ECON--+EC.MX-
5% for more than 2.5 minutes
but
less than 5.5 minutes and mechanical
cooling has not yet
started then:
4.
Lo Cool Mode mechanical
stages = 1
Hi Cool Mode mechanical
stages = 1
If the economizer
position is greater than (bnfiguration
--+ECON--)ECMX-
5% for more than 5.5 minutes
but
less than 8 minutes
and mechanical
cooling has started
42