Fire-Lite MS-9050UD Manual page 79

Addressable fire alarm control panel
Hide thumbs Also See for MS-9050UD:
Table of Contents

Advertisement

Master Programming Level
To change the programming for the displayed module, press the keyboard down arrow key to view
the following Edit Control screens:
Enable/Disable Module
EDIT CONTROL
1=ENABLED
To Enable or Disable the control module, press the 1 key while viewing the Edit Control Screen #2.
2=TYPE
Each press of the key will toggle the screen between Enabled Yes and Enabled No. If Enabled No
3=SILENCEABLE
is selected, the module will not be polled by the control panel, preventing the module from activat-
Edit Control Screen #2
ing its output devices. The control panel will indicate a system trouble condition and the Disable
LED will turn on if any devices are disabled.
Type
To select the type of control module being programmed, press the 2 key while viewing the Edit
Control Screen #2. This will cause the control panel to display the following Control Type Screens:
EDIT CONTROL
1=ENABLED
2=TYPE
3=SILENCEABLE
Edit Control Screen #2
MS-9050 Series Manual — P/N 52413:F 10/22/2010
EDIT CONTROL
1=ENABLED
2=TYPE
CONTROL
3=SILENCEABLE
Edit Control Screen #2
EDIT CONTROL
1=WALKTEST
2=ZONE ASSIGNMENT
00 ** ** ** **
Edit Control Screen #3
EDIT CONTROL
1=ADJECTIVE/NOUN
2=DESCRIPTION
********************
Edit Control Screen #4
CONTROL TYPE
1=BLANK
2=BELL-CIRCUIT
3=HORN-CIRCUIT
Control Type Screen #1
Programming
YES
YES
YES
79