Local/Remote Site Upload/Download
The Remote Download password (default 00000) must be entered to access the Remote Download
feature. Note that the default password can be changed using the Password Change option (refer to
"Password Change" on page 136). Entering the correct password will cause the following screen to
be displayed:
Pressing 1 for Proprietary No (factory default setting), while viewing the Remote Download
screen, will cause the display to toggle from Proprietary No to Proprietary Yes. Each press of the 1
key will cause the display to toggle between Proprietary No and Proprietary Yes. Selecting Propri-
etary Yes will program the FACP to allow remote programming downloads from the PS-Tools pro-
gramming utility at all times without the need to access the Remote Download screen.
Pressing 2 for Accept Download will cause the following screen to be displayed:
While this screen is displayed, remote programming downloads are allowed regardless of the Pro-
prietary setting. Exiting this screen will disable any further downloads to the FACP. Also, follow-
ing 30 minutes of inactivity (including up/downloading), the Accept Download screen will time-
out, causing the display to return to the System All Normal screen.

6.2 Transferring a Program

The first time that the control panel is contacted, a secret code is loaded in by a Service Terminal.
Future upload or download requests cause verification of the secret code by the control panel
before processing of data is allowed. If the secret code is not verified, the control panel will termi-
nate the request.
While the control panel is communicating with the remote Service Terminal, one of the DACT's
red phone line active LEDs and the green Kissoff LED will remain on steady. These LEDs do not
light for local (direct connect) programming.
In order to download to the panel, the following must be true:
The control panel must be in the Normal Mode of operation. Downloading is not allowed if
the panel is in any other mode.
There cannot be any active communications ongoing with a Central Station receiver.
All active events must be successfully 'kissed-off' by the Central Station(s). The
communicator must be in a standby state with no new information waiting to be transmitted
to a Central Station.
178
REMOTE DOWNLOAD
1=PROPRIETARY
2=ACCEPT DOWNLOAD
*ALLOWING DOWNLOADS*
IF YOU EXIT THIS
SCREEN DOWNLOADS
WILL BE DISABLED!
MS-9050 Series Manual — P/N 52413:F 10/22/2010