Programming
3.6.9 Option Modules
Options available for the MS-9050UD include annunciators, printer connection for acquiring hard-
copy printouts of panel data and onboard DACT.
Pressing 3 while viewing Programming Screen #3 will display the following screen:
PROGRAMMING
1=HISTORY
2=WALKTEST
3=OPTION MODULES
Programming Screen #3

ANN-BUS

Pressing 1 while viewing the Option Modules screen will cause the control panel to display the fol-
lowing screens.
A printer module and LCD annunciator module can be programmed into the MS-9050UD system.
These devices communicate with the FACP over the ANN-BUS terminals on the control panel.
The ANN-BUS must be enabled if any modules are connected to the ANN-BUS terminals. To
enable the ANN-BUS, press 1 while viewing ANN-BUS screen #1 so that the display reads ANN-
BUS Enabled Yes. Each press of the 1 key will cause the display to toggle between ANN-BUS
Enabled Yes and ANN-BUS Enabled No. The factory default setting is ANN-BUS Enabled No.
108
1=ANN-BUS
2=ONBOARD DACT
1=ENABLED
2=MODULES
3=AUTO-CONFIGURE
1=ANN-S/PG OPTIONS
2=ANN-80 OPTIONS
3=ANN-SECONDARY
ANN-BUS Enabled
OPTION MODULES
Options Screen
ANN-BUS
INSTALLED
ANN-BUS Screen #1
ANN-BUS
ANN-BUS Screen #2
MS-9050 Series Manual — P/N 52413:F 10/22/2010
Master Programming Level
NO