Section 1: Product Description

The MS-9050UD is a combination FACP (Fire Alarm Control Panel) and DACT (Digital Alarm
Communicator/Transmitter) all on one circuit board. This compact, cost effective, intelligent
addressable control panel has an extensive list of powerful features. The combination of Fire-Lite's
newer series devices and legacy 300 Series devices, along with the MS-9050UD FACP, offer the
latest in fire protection technology. The power supply and all electronics are contained on a single
circuit board housed in a metal cabinet, providing a complete fire control system for most applica-
tions. Available accessories include local and remote upload/download software, remote annuncia-
tors and reverse polarity/city box transmitter.
The integral DACT transmits system status (alarms, troubles, AC loss, etc.) to a Central Station via
the public switched telephone network. It also allows remote programming or interrogation of the
control panel using the PS-Tools Upload/Download utility via the public switched telephone net-
work. Any personal computer with Windows
of 2400 baud or faster and Upload/Download software kit PK-CD, containing PS-Tools, may serve
as a Service Terminal. This allows download of the entire program or upload of the entire program,
history file, walktest data and current status.
The MS-9050UDC is a ULC-approved Canadian version of the FACP which offers the same fea-
tures as the MS-9050UD, but is supplied standard with a dress panel and one built-in ANN-LED
annunciator. Refer to"Canadian Option" on page 104 for a full description.
The MS-9050UDE offers the same features as the MS-9050UD but allows connection to 220/240
VAC power.
NOTE: Unless otherwise specified, the terms FACP and MS-9050UD are used in this manual to
refer to all versions of the FACPs.
Inventory
When the MS-9050UD shipment is received, check to make certain that all parts have been
included in the shipment. The MS-9050UD shipment should consist of one of each of the follow-
ing:
main circuit board with display
chassis with transformer
backbox with door
plastic bag containing screws, cables, key, etc.
manual

1.1 Features and Options

Built-in DACT (Digital Alarm Communicator/Transmitter) with remote upload/download
Single addressable SLC loop which meets NFPA Style 4, 6 and 7 requirements
50 addressable device capacity (any combination of addressable detectors and addressable
control/relay/monitor modules totalling 50)
20 software zones
Two onboard NACs (Notification Appliance Circuits) which can be configured as Style Y
(Class B) or Style Z (Class A) circuits
2.5 amps total output power
Two programmable relays and one fixed trouble relay
Built-in Programmer
Telephone Line Active LEDs
12
®
XP or newer, and compatible modem with a speed
MS-9050 Series Manual — P/N 52413:F 10/22/2010

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ms-9050udc

Table of Contents