Programming

Disable

Pressing 2 for Disable, while viewing Zone Setup Screen #1, displays the following:
ZONE SETUP
1=ENABLE
2=DISABLE
3=ZONE 17 18 19
Zone Setup Screen #1
This screen allows the programmer to disable zones, one at a time. A flashing cursor appears next
to the Z, prompting the programmer to enter a two digit zone number (01 - 19). When the second
digit is entered, the zone will be disabled and the cursor will return to the original position next to
the Z. Another zone can then be disabled.

Zone 17, 18, and 19

Pressing 3 for Zone 17, 18, and 19, while viewing Zone Setup Screen #1, will display the following
screen:
Zones 17, 18, and 19 can be programmed for normal zone operation or for special purpose applica-
tions. In the above illustration, the three zones are shown Off, which means they can be pro-
grammed to function in the same manner as all other zones, by assigning them to input and output
devices in the Programming Zone Assignment Screen.
Pressing 1 will cause the display to change to PAS 17 On. Each press of the 1 key will cause the
display to toggle between PAS 17 On and PAS 17 Off. When Zone 17 is programmed On, a PAS
(Positive Alarm Sequence) activation of any smoke detector will cause Zone 17 to activate. By
assigning Zone 17 to a control module in the Programming Zone Assignment Screen, an output
device connected to the control module can be used to indicate a PAS condition in the control
panel. Do not assign Zone 17 to a Notification Appliance Circuit when using this zone to indicate a
PAS condition. Attempting to do so will generate an error message and will be prevented by soft-
ware checks.
Pressing 2 will cause the display to change to Pre-signal 18 On. Each press of the 2 key will cause
the display to toggle between Pre-signal 18 On and Pre-signal 18 Off. When Zone 18 is pro-
grammed On, a Pre-signal activation of any device will cause Zone 18 to activate. By assigning
Zone 18 to a control module in the Programming Zone Assignment Screen, an output device con-
nected to the control module can be used to indicate a Pre-signal condition in the control panel. Do
not assign Zone 18 to a Notification Appliance Circuit when using this zone to indicate a Pre-signal
condition. Attempting to do so will generate an error message and will be prevented by software
checks.
Pressing 3 will cause the display to change to Two Stage 19 On. Each press of the 3 key will cause
the display to toggle between Two Stage 19 On and Two Stage 19 Off. Refer to "Two Stage Opera-
tion" on page 101 for a description of this feature.
86
ZONE TO DISABLE
Z
Disable Screen
SPEC PURPOSE ZONE
1=PAS 17
2=PRE-SIGNAL 18 OFF
3=TWO STAGE 19
Zone 17, 18, and 19 Screen