Programming
ON BOARD DACT
1=SUPERV PHONE LINE
On Board DACT Screen #3
3.6.10 Password Change
PROGRAMMING
1=PASSWORD CHANGE
2=CLEAR PROGRAM
3=PROGRAM CHECK
Programming Screen #4
136
Phone Line Supervision
Pressing 1 while viewing On Board DACT Screen #3 will cause the following screen to be dis-
played:
1=PHONE LINE 2
The Phone Line 2 option allows the programmer to select whether the second phone line is super-
vised. Pressing 1 while viewing the On Board DACT Screen #3 causes the display to toggle
between Yes and No. The factory default setting is Yes.
The factory set passwords, which have been programmed into the control panel, can be changed by
selecting the Password Change option. Pressing 1 while viewing Programming Screen #4 will
cause the following screen to be displayed:
1=MASTER
2=MAINTENANCE
3=REMOTE DOWNLOAD
Press 1 to change the Master Programming Level password, 2 to change the Maintenance Level
password or 3 to change the Remote Download password. Note that the passwords will not be dis-
played on annunciators.
The following screen will appear when one of the change options is selected:
ENTER NEW FIVE DIGIT
A flashing cursor will appear in the center of the display. Enter a new five digit password (such as
10101 for the Master Level). After the fifth digit is entered, the following screen will be displayed:
SUPERVISE PHONE LINE
PASSWORD CHANGE
Password Change Screen
PASSWORD
Enter Password Screen
VERIFY NEW
PASSWORD
Password Change Screen
MS-9050 Series Manual — P/N 52413:F 10/22/2010
Master Programming Level
YES