Timers - Fire-Lite MS-9050UD Manual

Addressable fire alarm control panel
Hide thumbs Also See for MS-9050UD:
Table of Contents

Advertisement

Master Programming Level
SYSTEM SETUP

1=TIMERS

2=NAC
3=RELAYS
System Setup Screen #2
TIMERS
1=PAS DELAY
000
2=PRE SIGNAL
000
3=WATERFLOW
000
Timer Screen #1
MS-9050 Series Manual — P/N 52413:F 10/22/2010
Timers
Timer delays for PAS, Pre-signal and waterflow activation can be programmed by pressing 1 while
viewing System Setup Screen #2. The following screen will be displayed:
1=PAS DELAY
2=PRE SIGNAL
3=WATERFLOW
1=AC LOSS DELAY
PAS (Positive Alarm Sequence) Delay
The factory default setting for PAS is 000 for no delay. To select a PAS delay of 001 to 180 seconds
for all devices programmed for PAS, press 1 while viewing Timer Screen #1. The following dis-
play will appear:
RANGE 0-180 SECONDS
A flashing cursor is positioned in the lower left corner of the display. Enter a delay time consisting
of three digits, such as 005 for five seconds. Upon entering the third digit, the time delay will be
stored in the control panel memory and the display will return to the Delay Screen which will indi-
cate the new delay time.
TIMERS
000
000
000
Timer Screen #1
TIMERS
000
Timer Screen #2
PAS DELAY
PAS Delay Screen
Programming
95

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ms-9050udc

Table of Contents