Master Programming Level
EDIT MONITOR
1=PRE-SIGNAL
Edit Monitor Screen #3
EDIT MONITOR
1=WALKTEST
2=ZONE ASSIGNMENT
00 ** ** ** **
Edit Monitor Screen #4
MS-9050 Series Manual — P/N 52413:F 10/22/2010
User-Defined-14
Trouble-Monitor
User-Defined-15
3
Proc-Mon
User-Defined-16
3, 4
Procmon-AR
User-Defined-17
Future Use
Future Use
Ack-Switch
Sil-Switch
Reset-Switch
Drill-Switch
PAS-Bypass
5
HVAC RESTART
4
Drill-Switch AR
1 Conventional 2-wire smoke detectors may be powered using an external power supply
with an SLC Control Relay Module programmed for Resettable Power operation. A
Control Relay Module set to the Resettable Power type will follow the main circuit
board 24 VDC resettable power unless the control module is disabled.
2 Use only these Monitor Type IDs for the Zone Modules (MMF-302). The Zone
Modules will not function correctly if any other Type ID is used.
3 Combination systems employing these non-fire monitor types require the SLC loop to
be programmed by the installer for Style 4 operation and isolator modules must be
employed on each non-fire branch of the SLC as per Figure 13 in the Fire-Lite SLC
Wiring Manual (document number 51309). Fire and non-fire devices must not be used
on the same SLC branch.
4 For entries ending in AR, AR refers to AutoResettable.
5 For HVAC RESTART AND HVAC OVRRIDE descriptions, refer to"HVAC Control" on
page 201.
6 Drill Switch Auto-Resettable turns on the NACs and any control module mapped to the
Drill Switch zone.
Pre-signal
To enable the Pre-signal feature, press 1 while viewing Edit Monitor Screen #3 until the display
reads Pre-signal Yes. Each press of the 1 key will cause the display to toggle between Pre-signal
Yes and Pre-signal No. Refer to"Presignal" on page 156 for additional information.
Walktest
The Walktest feature allows one person to test the system devices without the necessity of manually
resetting the control panel after each device activation. To enable devices, which are connected to
a monitor module, for the Walktest feature, press 1 while viewing the Edit Monitor Screen #4 until
the display reads Walktest Yes. Each press of the 1 key will cause the display to toggle between
Walktest Yes and Walktest No. Refer to"Walktest" on page 158 for additional information.
Zone Assignment
A maximum of five zones can be programmed to each addressable monitor module. Pressing 2
while viewing Edit Monitor Screen #4 displays the following screen:
Z00 Z** Z** Z** Z**
AC Fault
Trouble
Trouble
Piezo
Piezo
Piezo, nonlatching (tracking)
Piezo, nonlatching (tracking)
Future Use
Future Use
Acts like panel Acknowledge Key
Acts like panel Alarm Silence Key
Acts like panel Reset Key
Acts like panel Drill Key
PAS Disable
Switch
Acts like panel Drill Key, nonlatching (tracking)
Table 3.1 Monitor Types
MON ZONE ASSIGN
Zone Assignment Screen
Programming