Appendix G: Ademco Contact Id Format Event Code Descriptions; G.1: Transmission Format Between Dact And Receiver; G.2: Ademco Contact Id Typical Printout - Fire-Lite MS-9050UD Manual

Addressable fire alarm control panel
Hide thumbs Also See for MS-9050UD:
Table of Contents

Advertisement

Appendix G: Ademco Contact ID Format Event Code
This appendix describes the various Event Codes and their messages which are available for the
Ademco Contact ID Format.
G.1 Transmission Format Between DACT and Receiver
The transmission string for the Ademco Contact ID Format is as follows:
SSSS 18 QXYZ GG CCC where
SSSS
18
Q
XYZ
GG
CCC
Notes:
1.
18, which is used in the reporting structure to identify the transmission as Contact ID, is not
printed out in the alarm and trouble report.
2.
GG Group Number is fixed at '00' and cannot be changed.
3.
CCC for Zone or Point Number:
Zone Number is transmitted as '00' for zone 0 up to '19' for zone 19
Point Number is transmitted as '01' for point/address 1 up to '50' for point/address 50
G.2 Ademco Contact ID Typical Printout
A typical printout from a Central Station receiver (such as the Ademco 685) of alarm and trouble
reports in the Ademco Contact ID Reporting Structure follows:
Time
Date
Rcvr/Line ID SSSS
11:28
03/25
11:28
03/25
11:28
03/25
11:28
03/25
11:28
03/25
11:28
03/25
11:28
03/25
11:28
03/25
11:28
03/25
11:28
03/25
Notes:
1.
11 is an example of a Receiver/Line Card, showing which receiver and line card the message
was transmitted to.
2.
Q, which is the Event Qualifier for the reporting structure, is printed out in the report as an E
for New Event or R for New Restore.
MS-9050 Series Manual — P/N 52413:F 10/22/2010
Descriptions
= Four digit Subscriber ID Account Code
= Identifies transmission as Contact ID to the receiver at the Central Station
= Event Qualifier where 1 = New Event and 3 = New Restore
= Event code
= Group number
= Zone/Point number
QXYZ
11
7777
E110
11
7777
E111
11
7777
E380
11
7777
E570
11
7777
R110
11
7777
R111
11
7777
R380
11
7777
R570
11
7777
E158
11
7777
E151
GG
CCCC
00
C001 - general fire alarm on zone one
00
C002 - smoke detector alarm on zone two
00
C003 - fault on zone three
00
C009 - Zone nine disabled
00
C001 - Zone one alarm restored
00
C002 - smoke detector zone two restored
00
C003 - zone three fault restored
00
C009 - zone nine reenabled
00
C006 - high temperature, zone six
00
C007 - gas detected, zone seven
203