Initial Power-Up; Programming Screens Description; Programming And Passwords - Fire-Lite MS-9050UD Manual

Addressable fire alarm control panel
Hide thumbs Also See for MS-9050UD:
Table of Contents

Advertisement

Programming
User Programming Levels
There are two user programming levels:
User Master Program Level 1 is used for programming panel specific data relating to device
types, zoning, messages, control panel functions, etc.
User Maintenance Program Level 2 is used by a qualified operator to access features such as
Disable/Enable, View and Clear History, Walktest and System Time Change.

3.3 Initial Power-up

The following sections describe the initial programming procedures for a new system. The same
procedures are used to modify programming in an existing system.
After completing the wiring of addressable devices to the SLC, apply power to the control panel. If
the addressable devices have not yet been programmed into the FACP, their LEDs will not flash and
the following trouble message will be displayed.

3.4 Programming Screens Description

Four options are available when the Enter key is pressed: Read Status, Programming, Manual Dial
Mode and Remote Download. The Read Status and Programming options have multiple functions
or features which may be chosen. To view all of the choices, it is necessary that the programmer
scroll through a number of additional subscreens. These selections are displayed on multiple
screens to make them more readable for the programmer. Refer to "Master Programming Level"
on page 56, for additional information on the various screens.
The title of the main option screen will always be displayed at the top of the subscreens for the pro-
grammer's convenience. If additional subscreens exist, an Up or Down arrow will be displayed in
the upper right corner of the screen being viewed. The programmer can then press the keypad Up
or Down arrow key to view the new subscreen. To select one of the choices in a screen, the pro-
grammer presses the keypad numerical key corresponding to the desired choice.
Note that subscreens may also have multiple options which require viewing more than one screen.
The same process, as detailed in the previous paragraphs, is followed to view all option choices.

3.5 Programming and Passwords

There are two factory set programming passwords which will access the Programming screens as
indicated in the following examples. From either of the screens, access to specific system and
device features or programming may be obtained. All user programming entries are stored in non-
volatile memory. The factory set passwords can be changed by the user as described in "Password
Change" on page 136. If an invalid password is entered, the blinking cursor will return to the first
password character position. To exit Programming, Read Status, Manual Dial mode or Remote
Download at any time, press the ESC (Escape) key repeatedly. Note that Programming mode must
be exited using the ESC key in order to store the program data entered during this mode. If the
Reset key is pressed or power is lost before exiting Programming mode, the data just entered will
not be saved.
54
TROUBL IN SYSTEM
NO DEVICES INSTALLED
09:03A 012110
MS-9050 Series Manual — P/N 52413:F 10/22/2010
Initial Power-up

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ms-9050udc

Table of Contents