■ Correcting Linear Output Values
Discrepancies may occur between the linear output current (or voltage) values set on
the Sensor Controller and the actual current (or voltage) values measured due to the
conditions for the connected external device or other factors. The linear output correc-
tion function can be used to correct this discrepancy.
The output values are corrected by entering the correction value for the current (or volt-
age) values for any two points. (default value: OFF)
Range: -999 to 999
Set the focus function and select either current or voltage output beforehand. Also, connect the lin-
ear output to an external ammeter or voltmeter.
FUN mode-[I/O SET]-[ANALOG]-[ADJUST]-[ON]
1.
Set the output value of point 1.
The output value is displayed on the main display.
2.
Press the SET Key to apply the setting.
3.
Set the correction value for point 1.
The measurement value is displayed on the sub-dis-
play.
Adjust the correction value on the sub-display so that
the ammeter (or voltmeter) reading and the output
value shown on the main display are the same.
4.
Press the SET Key to apply the setting.
5.
Set point 2 in the same way as point 1.
If the points are not set correctly, check to see if the cur-
rent (or voltage) values of points 1 and 2 are the same.
ZS-L
4-4
User's Manual
INPUT POINT 1
CHANGE SET:OK
INPUT POINT 1
DIG
VAL SET:OK
INPUT POINT 2
DIG
VAL SET:OK