Section 2
About the I/O cable
(7) OUT4 (BUSY output)
This turns ON during sampling with the hold function enabled. It allows you to check
whether or not the self-trigger is functioning correctly. It also turns ON during bank
switching.
(8) Linear output
The linear output outputs a current or voltage in accordance with the measured value.
(9) Linear GND
The linear GND terminal is the 0V terminal for the linear output.
This ground wire must be grounded separately from the other ground wires.
Always ground the linear output terminal even when linear output is not used.
(10) to (13) IN0 to IN3
The following input signal assignments can be selected.
• Signal assignments
Signal
IN0
IN1
IN2
IN3
I/O Assignment Settings p.4-7
• Signal functions
Signal Name
External trigger (timing) input
Reset input
LD-OFF input
Zero reset input
Bank input A, B
External I/O timing chart p.4-9
ZS-L
2-8
User's Manual
When [Standard] is selected (default)
External trigger (timing) input
Reset input
LD-OFF input
Zero reset input
Description
This timing input is for signal input from external devices. Use it for hold
function timing.
This resets all executing measurements and outputs. While a reset is
being input, judgment output conforms to the non-measurement set-
ting. If this reset input switches ON while the hold function is used, the
state in effect before the hold function was set will be restored.
If this LD-OFF signal is set to ON, the laser will stop emission, causing
a light amount error. While LD-OFF is being input, judgment output
conforms to the non-measurement setting.
This is used to execute and clear a zero reset.
This is used for switching banks. Specify the bank No. in combinations
of A and B.
When [Bank] is selected
Bank input A
Bank input B
LD-OFF input
Zero reset input