Using Output Signals

(n057, n058, n059)
The functions of multi-function output terminals MA, MB, P1 and P2
can be changed as necessary by setting constants n057, n058, and n059.
• Terminal MA and MB functions: Set in n057
• Terminal P1 function: Set in n058
• Terminal P2 function: Set in n059
Setting
0
Fault
1
Operating
2
Frequency agree
3
Zero speed
4
Frequency detection 1
5
Frequency detection 2
6
Overtorque detection,
NO contact output
7
Overtorque detection,
NC contact output
8
Undertorque detected,
NO contact output
9
Undertorque detected,
NC contact output
10
Minor fault
11
Base blocked
12
Operating mode
13
Inverter operation
ready
14
Fault retry
118
Name
Closed when Inverter fault occurs.
Closed when either FWD/REV Run
Command is input or voltage is output
from the Inverter.
Closed when the set frequency agrees
with Inverter output frequency.
Closed when Inverter output frequency
is less than minimum output frequency.
Output frequency
tion Level (n095)
Output frequency Frequency Detec-
tion Level (n095)
Closed when an alarm has been de-
tected.
Closed when the Inverter output is
OFF.
Closed when LOCAL is selected for the
LOCAL/REMOTE selection.
Closed when an Inverter fault is not de-
tected, and operation is ready.
Closed during fault retries.
Description
Frequency Detec-
-
-
-
-
Ref.
page
-
-
119
-
77
77
76
76
179
179
-
-
-
-
-