Stall Prevention during Operation

Stall Prevention above Base Speed during Run (n115)
The stall prevention level can be decreased automatically in the constant
output range.
Constant
No.
n115
Stall Prevention above
Base Speed during Run
n115 Settings
Setting
0
The stall prevention level is the level set for constant n094
in all frequency areas.
1
The following figure shows how the stall prevention level is
automatically decreased in the constant output range
(Max. frequency Max. Voltage Output Frequency (n013)).
The lower limit is 40% of the set value of n094.
Operation Level
n094
40% of n094
Acceleration/Deceleration Time Selection during Stall Pre-
vention (n116)
With this function, Acceleration Time 2 (n021) and Deceleration Time 2
(n022) can be fixed as the acceleration/deceleration time when moving
to prevent stalling during operation.
Constant
No.
n116
Acceleration/Deceleration
Time Selection during
Stall Prevention
Name
Function
Constant Output Area
Operation Level
n094
n013
Name
6 Programming Features
Unit
Setting
Range
-
0=Disabled
1=Enabled
Max. Voltage Output Frequency n013
Output Frequency
Lower Limit
Output Frequency
Unit
Setting
Range
-
0=Disabled
1=Enabled
Factory
Setting
0
Factory
Setting
0