Frequency
reference
FWD (REV) Run/Stop
Multi-step speed ref. 1
(terminal S5)
Multi-step speed ref. 2
(terminal S6)
Multi-step speed ref. 3
(terminal S7)
n050 = 1 (Input terminal S1) (factory setting)
n051 = 2 (Input terminal S2) (factory setting)
n052 = 3 (Input terminal S3) (factory setting)
n053 = 5 (Input terminal S4) (factory setting)
n054 = 6 (Input terminal S5) (factory setting)
n055 = 7 (Input terminal S6) (factory setting)
n056 = 8 (Input terminal S7) (Change the setting to 8.)
16-step speed operation
Set frequency references 9 to 16 for n120 to n127.
Set the input terminal for a multi-step speed reference using the multi-
function input selection.

Operating at Low Speed

By inputting a Jog Command and then a Forward (Reverse) Run Com-
mand, operation is enabled at the jog frequency set in n032. When
multi-step speed references 1, 2, 3 or 4 are input simultaneously with
the Jog Command, the Jog Command has priority.
Constant No.
n032
n050 to n056
70
(n028) 45.0 Hz
(n027) 40.0 Hz
(n026) 35.0 Hz
(n025) 30.0 Hz
(n024) 25.0 Hz
Name
Jog Frequency
Jog References Set to 10 for any constant.
(n031) 60.0 Hz
(n030) 55.0 Hz
(n029) 50.0 Hz
Setting
Factory setting: 6.00 Hz