Advertisement

Up/Down Command 2 by time and return to original frequency
reference when S6, S7 = OFF
n056 = 36
n003 = 1
n004 = 1
n045 = 0
n046 = 1
n047 = 1
n100 = 1
Fout (HZ)
35 Hz
Accel 1
10 Hz
RUN command
UP 2 Command
DOWN 2 Command
Multi-step speed
n 024 (35 Hz)
command

Using the Multi-function Analog Inputs

(n077, n078, n079)
The input analog signal (0 to 10 V or 4 to 20 mA) for the CN2 terminal
of the JVOP-147 Digital Operator can be used as an auxiliary function
for the master frequency reference input to the control circuit terminals
(FR or RP). Refer to the block diagram on page 161 for details on the
input signal.
NOTE
Up/Down command 2 on S6 / S7
Run command source is digital input
Main frequency reference input is n024
Frequency reference bias is changed by time
Use Acceleration / Deceleration time 4
Bias value is held if S6, S7 are both ON or OFF
Bias value is saved to EEPROM
Decel 4
Accel 1
When using the signal for the CN2 terminal of the JVOP-147
Digital Operator as a multi-function analog input, never use it
for the target value or the feedback value of PID control.
6 Programming Features
Decel 1
Accel 4
n 025 (10 Hz)
Decel 1
Accel 1
Decel 1
TIME
n 024 (35 Hz)