Copy Function - Omron V7-IP65 User Manual

Compact sensorless vector inverter
Hide thumbs Also See for V7-IP65:
Table of Contents

Advertisement

COPY Function

This function writes the constants stored inside the Digital Operator in
batch to the Inverter. Write-in is possible only for Inverters with the
same product series, power supply specifications, and control mode (V/
f control or vector control).
Therefore, writing from 200 V Class to 400 V Class Inverters (or vice
versa), from V/f control mode to vector control mode Inverters (or vice
versa), or from V7 IP65 to VS mini J7 Inverters is not possible.
The Constant Copy Function Selection (n176), Constant Read Selection
Prohibit (n177), Fault History (n178), Software Version No. (n179), and
hold output frequency are not written. vAE will appear (flashing) if the
capacities of the Inverters differ.
Press
ENTER
Press
STOP/RESET
The following constants are not written if the Inverter capacities differ.
Constant No.
V/f Settings
n011 to n017
Motor Rated Current
n036
Carrier Frequency Se-
n080
lection
Torque Compensation
n105
Iron Loss
Motor Rated Slip
n106
Motor Line-to-neutral
n107
Resistance
Constants added with software version upgrades will not be written
between V7 IP65 Inverters without the additional constants and
V7 IP65 Inverters with the additional constants.
For this reason, the settings for the additional constants will not be
changed by the copy operation.
166
to continue writing (the COPY function).
to stop the COPY function.
Name
Constant No.
Motor Leakage Induc-
n108
tance
Torque Compensa-
n109
tion Voltage Limiter
Motor No-load Current
n110
Energy-saving Coeffi-
n140
cient K2
Motor Code
n158
Name