Initial Setting
4-1-2

Software Settings

Disabling DeviceNet Communications (Standalone)
IMPORTANT
66
When DeviceNet Communications are disabled, the NE1A-series Controller
stops all DeviceNet communications and operates as a Standalone Control-
ler. The default is to have DeviceNet communications enabled (normal mode).
Make the setting from the Network Configurator. After the setting has been
made, a reset command will be sent from the Network Configurator to the
NE1A-series Controller to enable the setting.
Setting
Enabled (Normal Mode)
Disabled (Standalone Mode)
• When DeviceNet communications are disabled, connect the NE1A-series
Controller to the Network Configurator via a USB connection or via Ether-
Net/IP (for Controllers that support EtherNet/IP).
• When DeviceNet communications are disabled, operation using the Net-
work Configurator can be performed via a USB connection or via Ether-
Net/IP (for Controllers that support EtherNet/IP).
Description
DeviceNet communications enabled.
DeviceNet communications disabled. The SNC will
operate as a Standalone Controller. "nd" will be displayed on
the 7-segment display.
Section 4-1