Specifications
2-2-2

DeviceNet Communications Specifications

Item
Communications
protocol
Connection method
Baud rate
Communications
medium
Communications
distance
Communications power
supply
Connected nodes
Safety I/O
communications
(Pre-Ver. 1.0 Controllers)
Safety I/O
communications
(Controllers with unit ver-
sion 1.0 or later)
(including Controllers
that support EtherNet/
IP)
Standard I/O
communications
Message communica-
tions
2-2-3
EtherNet/IP Communications Specifications (Controllers That
Support EtherNet/IP)
Item
Media access method
Modulation method
Transmission path type
Baud rate
Transmission medium
Transmission distance
Number of cascade connections
Conforms to DeviceNet.
The multidrop and T-branch connections can be combined (for main line and branch lines).
500 kbits/s, 250 kbits/s, 125 kbits/s
Special cable with 5 lines (2 communications lines, 2 power lines, 1 shield line)
Baud rate
500 kbits/s
250 kbits/s
125 kbits/s
The numbers in parentheses are the lengths when Thin Cable is used.
11 to 25 VDC
63 nodes max.
Safety Master Function:
• Maximum number of connections: 16
• Maximum data size: 16 bytes input or 16 bytes output (per connector)
• Connection type: Single-Cast, Multi-Cast
Safety Slave Function:
• Maximum number of connections: 4
• Maximum data size: 16 bytes input or 16 bytes output (per connector)
• Connection type: Single-Cast, Multi-Cast
Safety Master Function:
• Maximum number of connections: 32
• Maximum data size: 16 bytes input or 16 bytes output (per connector)
• Connection type: Single-Cast, Multi-Cast
Safety Slave Function:
• Maximum number of connections: 4
• Maximum data size: 16 bytes input or 16 bytes output (per connector)
• Connection type: Single-Cast, Multi-Cast
Standard Slave Function
• Maximum number of connections: 2
• Maximum data size: 16 bytes input and/or 16 bytes output (per connector)
• Connection type: Poll, Bit-strobe, COS, Cyclic
Maximum message length: 552 bytes
CSMA/CD
Baseband
Star topology
10Base-T: 10 Mbits/s
100Base-TX: 100 Mbits/s
Twisted-pair cable (shielded: STP): Category 5, 5e
100 m (distance between hub and nodes)
There is no limit when a switching hub is used.
Specifications
Maximum network length
100 m max. (100 m max.)
250 m max. (100 m max.)
500 m max. (100 m max.)
Specifications
Section 2-2
Branch length
Total length
6 m max.
39 m max.
6 m max.
78 m max.
6 m max.
156 m max.
35