11-3 Startup Time
Initialization Time
Time Until Start of Program Execution Depending on Unit Version
Unit Version 1.0
NE1A
Initialization:
SCPU01-V1: 7 s
SCPU02: 9 s
DST1
Initialization: 10 s
NE1A General Status Bit 6
(Operating Mode Flag)
Unit Version 2.0
NE1A
Initialization:
9 s
DST1
Initialization:
10 s
NE1A General Status
Bit 6 (Operating
Mode Flag)
Note
220
The NE1A-series Controller performs initialization when the power is turned
ON. During initialization, the Controller performs self-diagnosis of the hard-
ware that is required to execute safety functions. The following table shows
the times required to complete initialization from when the power is turned
ON.
Model
NE1A-SCPU01
None
NE1A-SCPU01-V1
1.0
2.0
NE1A-SCPU02
1.0
2.0
NE1A-SCPU01-EIP
1.0
NE1A-SCPU02-EIP
1.0
MS indicator: Lit green
Start of program execution
Wait for
Online processing:
DST1 online
2 s
processing
to start
Online processing:
3 or 4 s
Program execution
start (without program
execution start delay)
MS indicator: Lit green
Online wait: 5 s
NE1A online
processing start
delay
(1) With NE1A-series Controllers with unit version 2.0 (including Controllers
that support EtherNet/IP), an online delay time of 5 s is added after the
initialization has been completed to allow time for other devices to start.
(2) After the initialization has been completed, the NE1A-series Controller
checks for duplicated addresses on the DeviceNet network and then joins
the network (i.e., goes online). After the Controller connects to the net-
work, the NS indicator lights or flashes green. This processing takes a
maximum of 2 s.
Unit version
6 s
7 s
9 s
9 s
9 s
9 s
9 s
Connection
The NE1A-series Controller
established
establishes a connection with
each DST1-series Safety
Slave, and starts I/O
communications as soon as it
Connection
connects to each Slave.
established
Program execution start
delay time: 20 s max.
Online processing:
Connection established
2 s
Online processing:
Connection
3 or 4 s
established
Section 11-3
Initialization time
Program execution
start (with program
execution start delay)