Precautions For Safe Use - Omron NE1A-SCPU01 - 07-2009 Operation Manual

Safety network controller
Hide thumbs Also See for NE1A-SCPU01 - 07-2009:
Table of Contents

Advertisement

Precautions for Safe Use

Control device
Contactor
Other devices
4
Precautions for Safe Use
Use contactors with a forcibly guided mechanism and monitor the auxiliary
NC contact to detect contactor failures. For feedback signals, use devices
with contacts capable of switching micro-loads of 4 mA at 24 VDC.
Evaluate whether devices used are appropriate to satisfy the requirements of
the safety category level.
Handling with Care
Do not drop the NE1A-series Controller or subject it to excessive vibration or
mechanical shock. The NE1A-series Controller may be damaged and may not
function properly.
Installation and Storage Environment
Do not use or store the NE1A-series Controller in any of the following loca-
tions:
• Locations subject to direct sunlight
• Locations subject to temperatures or humidity outside the range specified
in the specifications
• Locations subject to condensation as the result of severe changes in tem-
perature
• Locations subject to corrosive or flammable gases
• Locations subject to dust (especially iron dust) or salts
• Locations subject to water, oil, or chemicals
• Locations subject to shock or vibration
Take appropriate and sufficient measures when installing systems in the fol-
lowing locations. Inappropriate and insufficient measures may result in mal-
function.
• Locations subject to static electricity or other forms of noise
• Locations subject to strong electromagnetic fields
• Locations subject to possible exposure to radioactivity
• Locations close to power supplies
Installation and Mounting
• Use the NE1A-series Controller within an enclosure with IP54 protection
or higher according to IEC/EN 60529.
• Use DIN rail (TH35-7.5/TH35-15 according to IEC 60715) to install the
NE1A-series Controller into the control panel. Mount the NE1A-series
Controller to the DIN rail using PFP-M End Plates (not included with the
NE1A-series Controller) to prevent it falling off the DIN rail because of
vibration.
• Space must be provided around the NE1A-series Controller, at least 5
mm from its side and at least 50 mm from its top and bottom surfaces, for
ventilation and wiring.
Installation and Wiring
• Use the following to wire external I/O devices to the NE1A-series Control-
ler.
Solid wire
0.2 to 2.5 mm
Stranded (flexi-
0.34 to 1.5 mm
ble) wire
Requirements
2
(AWG 24 to AWG 12)
2
(AWG 22 to AWG 16)
4
xxi