Main Functions - Omron E5AN User Manual

Digital temperature controllers
Hide thumbs Also See for E5AN:
Table of Contents

Advertisement

I/O Configuration and Main Functions
Model Number Structure
Model Number Legends
1-2-2

Main Functions

Input Sensor Types
12
Controllers
E5GN-@@@@@-@-@-@
1 2
3 4 5
1. Control Output 1
R: Relay output
Q: Voltage output (for driving SSR)
C: Current output
2. Auxiliary Outputs
Blank: None
1: One outputs
2: Two outputs
3. Option
Blank: None
01: RS-232C communications
03: RS-485 communications
B: Two event inputs
H: Heater burnout/Heater short/Heater overcurrent
detection (CT1)
4. Input Type
T: Universal thermocouple/platinum resistance
thermometer input
L: Analog current/voltage input
5. Power Supply Voltage
Blank: 100 to 240 VAC
D: 24 VAC/VDC
6. Terminal Type
Blank: Models with Screw Terminal Blocks
C: Models with Screwless Clamp Terminal Blocks
7. Case Color
Blank: Black
W: Silver
8. Communications Protocol
Blank: None
FLK: CompoWay/F communications
Note
Silver is available by special order only.
This section introduces the main E5CN/CN-U/AN/EN/GN functions. For
details on particular functions and how to use them, refer to SECTION 3 Basic
Operation and following sections.
• The following input sensors can be connected for temperature input
(i.e., E5_N-@@@@T):
Thermocouple:
Infrared temperature sensor:
Platinum resistance thermometer: Pt100, JPt100
Analog input:
6
7
8
K, J, T, E, L, U, N, R, S, B, W, PLII
ES1B
10 to 70 C, 60 to 120 C, 115 to 165 C,
140 to 260 C
0 to 50 mV
Section 1-2

Advertisement

Table of Contents
loading

This manual is also suitable for:

E5cnE5enE5gn

Table of Contents