Note
(1) The indication accuracy of K thermocouples in the 200 to 1,300 C range, T and N thermocouples
at a temperature of 100 C or less, and U and L thermocouples at any temperature is 2 C 1 digit
maximum. The indication accuracy of B thermocouples at a temperature of 400 C to 800 3 C or
less is not specified. The indication accuracy of R and S thermocouples at a temperature of 200 C
or less is 3 C 1 digit maximum. The indication accuracy of W thermocouples is (the larger of
0.3% or 3 C) 1 digit maximum and the indication accuracy of PLII thermocouples is (the larger
of 0.3% or 2 C) 1 digit maximum.
(2) Ambient temperature: 10 C to 23 C to 55 C
Voltage range: 15 to +10% of rated voltage
(3) Set "None" as the unit for Controllers with Analog Inputs.
Rating and Characteristics of Options
Event inputs
Communications
Transfer output
Waterproof Packing
If the Waterproof Packing is lost or damage, order one of the following models.
Y92S-29 (for DIN 48
Y92S-32 (for DIN 48
278
Contact Input
ON: 1 k max., OFF: 100 k min.
Non-contact Input
ON: Residual voltage 1.5 V max.; OFF: Leakage current 0.1 mA max.
Transmission path: RS-485/232C
Communications method: RS-485 (2-wire, half duplex) or RS-232C
Synchronization: Start-stop
Baud rate: 1.2, 2.4, 4.8, 9.6, 19.2, 38.4, or 57.6 kbps
4 to 20 mA DC, Load: 600
48)
24)
max., Resolution: 10,000, Accuracy: 0.3%
Y92S-P4 (for DIN 96
Y92S-P4 (for DIN 48