Communications Function
Note
Setting Communications
Data
Parameter name
Symbol
psel
Protocol Setting
u-no
Communications
Unit No.
bps
Communications
Baud Rate
len
Communications
Data Length
sbit
Communications
Stop Bits
prty
Communications
Parity
sdwe
Send Data Wait
Time
psel
Protocol Setting
cwf
M
u-no
Communications Unit No.
1
M
Communications Baud Rate
bps
9.6
M
Communications Data Length
len
(See note.)
7
M
sbit
Communications Stop Bits
(See note.)
2
M
prty
Communications Parity
even
M
Send Data Wait Time
sdwt
20
M
The Protocol Setting parameter is displayed only when CompoWay/F commu-
nications are being used.
Match the communications specifications of the E5CN/AN/EN/GN and the
host computer. If a 1:N connection is being used, ensure that the communica-
tions specifications for all devices in the system (except the communications
Unit No.) are the same.
Setting (monitor) value
CompoWay/F (SYSWAY),
Modbus
0 to 99
1.2, 2.4, 4.8, 9.6, 19.2,
38.4, 57.6
7, 8
1, 2
None, Even, Odd
0 to 99
Selection symbols
cwf, mod
1.2, 2.4, 4.8, 9.6, 19.2, 38.4.
57.6
none, even, odd
Section 1-4
Default
Unit
CompoWay/F
None
(SYSWAY)
1
None
9.6
kbps
7
Bits
2
Bits
Even
None
20
ms
19