(4-3) Initialized to the above default values regardless of the settings for changing the transfer out-
put type.
(5) Initialized as follows according to the Standard or Heating/Cooling parameter setting.
MV Upper Limit: 105.0
MV Lower Limit: Standard 5.0, heating/cooling 105.0
(6) Initialized to control output (cooling) for heating and cooling control, according to the following.
(The defaults for standard control are the defaults in the parameter list.)
With control output 2: The Control Output 2 Assignment parameter is initialized to control output
(cooling).
Without control output 2 and E5AN/EN: The Auxiliary Output 3 Assignment parameter is initialized
to control output (cooling).
Without control output 2 and E5CN: The Auxiliary Output 2 Assignment parameter is initialized to
control output (cooling).
E5GN: The Auxiliary Output 1 Assignment parameter is initialized to control output (cooling).
(7) When the program pattern is OFF, the Auxiliary Output 1 Assignment parameter is initialized to
alarm output 1. When the program pattern is not OFF, the Auxiliary Output 1 Assignment parameter
is initialized to program end output. The Auxiliary Output 1 Assignment parameter is not initialized
for the E5GN, however, if it is set for heating/cooling control.
(8) If the Program Start parameter is assigned when the program pattern is changed to OFF, the Pro-
gram Start parameter will be initialized to "not assigned."
(9) Initialized when temperature inputs are used and RT is changed. The defaults are as follows:
Proportional band: 8.0
Integral time: 233
Derivative time: 40 when RT is OFF, and 40.0 when RT is ON.
(10) The proportional band, integral time, and derivative time are initialized as follows by RT and input
type changes.
• When RT is turned from ON to OFF by a change from temperature input to analog input.
• When ON is turned to OFF or OFF is turned to ON by an RT change.
(11) Write to both so that the SP and the currently selected Multi-SP SP0 to SP3 match.
(12) Initializes event input assignments used for Multi-SP to NONE.
(13) Initialized to 0.8 when the temperature unit is C, and to 1.4 when the temperature unit is F.
302