Initial Setting Level
alt3
Alarm 3 Type
Function
Setting
See
See
tr-t
Transfer Output Type
Note
210
• Select one of the following four alarm 3 types:
Deviation, deviation range, absolute value, or PV change rate alarm.
Refer to the alarm 1 type list. The 12: LBA (Loop Burnout Alarm) setting in
that list cannot be used.
■ Related Parameters
Alarm value 3: Page 173, Alarm value upper limit 3, Alarm value lower limit 3:
Page 175 (operation level)
Standby sequence reset: Page 221, Auxiliary output * open in alarm: Page
222, Alarm 3 hysteresis: Page 209, Alarm 3 latch: Page 227 (advanced func-
tion setting level)
• This parameter sets the transfer output type.
• The operation is shown in the following table.
Transfer Output Destination
Control output 1
Current output
• Relay output
• Voltage output (for driving
SSR)
■ Precision and User Calibration
Transfer output
Simple transfer output
Refer to SECTION 6 CALIBRATION for details on the calibration procedure.
Alarm 3 must be assigned.
There must be a transfer output or a
current output.
Control output 2
• No
• Relay output
• Voltage output (for driving
SSR)
• No
• Relay output
• Voltage output (for driving
SSR)
Precision
0.3% FS
0.3% FS
Section 5-7
Transfer output
destination
Control output 1
No
User calibration
Supported (See note.)
Not supported.