Setting the PF Key
Set
value
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
Operating Procedure
Operation Level
PV/SP
C
25
100
Initial Setting Level
Input Type
in-t
5
Move to Ad-
amov
vanced Function
Setting Level
-169
142
Setting
Disabled
PV/SP/Multi-SP
PV/SP/MV (See note.)
PV/SP /Soak time remain
Proportional band (P)
Integral time (I)
Derivative time (D)
Alarm value 1
Alarm value upper limit 1
Alarm value lower limit 1
Alarm value 2
Alarm value upper limit 2
Alarm value lower limit 2
Alarm value 3
Alarm value upper limit 3
Alarm value lower limit 3
Note For details on MV settings for heating and cooling control, refer to
MV Display for Heating and Cooling Control on page 84.
Setting Monitor/Setting Items
Pressing the PF Key in either the operation or adjustment level displays the
applicable monitor/setting items. Press the PF Key to display in order Monitor/
Setting Items 1 to 5. After Monitor/Setting Item 5 has been displayed, the dis-
play will switch to the top parameter in the operation level.
Note
(1) Items set as disabled in the Monitor/Setting Items 1 to 5 parameters will
not be displayed, and the display will skip to the next enabled setting.
(2) While a monitor/setting item is being displayed, the display will be
switched to the top parameter in the operation level if the M Key or the
O Key is pressed.
This procedure sets the PF Setting parameter to PFDP, and the Monitor/Set-
ting Item 1 parameter to 7 (Alarm Value 1).
1. Press the O Key for at least three seconds to move from the operation
level to the initial setting level.
2. Select the Move to Advanced Function Setting Level parameter by press-
ing the M Key.
Monitor/Setting
Can be set. (SP)
Can be set. (SP)
Can be set. (SP)
Can be set.
Can be set.
Can be set.
Can be set.
Can be set.
Can be set.
Can be set.
Can be set.
Can be set.
Can be set.
Can be set.
Can be set.
Section 4-19
Remarks
Symbol
---
---
---
---
p
i
d
al-1
al1h
al1l
al-2
al2h
al2l
al-3
al3h
al3l