Adjustment Level
insh
Upper-limit Temperature Input Shift Value
insl
Lower-limit Temperature Input Shift Value
Function
Setting
See
See
These parameters are used to shift the input temperature at two points: an
upper-limit temperature and a lower-limit temperature (as opposed to the
Temperature Input Shift parameter, which shifts the input temperature by set-
ting the shift for only one point). A 2-point shift enables more accurate offset of
the input range compared with a 1-point shift if the input shift values at the
upper and lower limits differ.
This parameter sets input shift values for the upper and lower limits (2-point
shift) of the input range.
Setting range
199.9 to 999.9
C or F
■ Related Parameters
Input type (initial setting level): Page 200
Input shift type (advanced function setting level): Page 233
The Input Type parameter must be
set for a thermocouple or resistance
thermometer and the Input Shift Type
parameter must be set to a 2-point
shift, or the Input Type parameter
must be set for an infrared sensor.
Unit
Default
0.0
Section 5-4
187