Alarm Delays
Operating Procedure
Operation Level
PV/SP
C
25
100
Initial Setting Level
Input Type
in-t
5
Initial Setting Level
Move to Ad-
amov
vanced Function
Setting Level
0
Advanced Function Setting Level
Parameter
init
Initialization
off
Advanced Function Setting Level
Alarm 1 ON
a1on
Delay
0
a1on
5
Advanced Function Setting Level
Alarm 1 OFF
a1of
Delay
0
a1of
10
Initial Setting Level
Input Type
in-t
5
Note
(1) The defaults are 0, i.e., the ON and OFF delays are disabled.
(2) The parameters are displayed when alarm functions are assigned and
when the alarm type is set to any type but 0 (none), 12: LBA, or 13: PV
change rate alarm.
Use the following procedure to set ON and OFF delays for the alarm 1.
An ON delay of 5 seconds and an OFF delay of 10 s will be set.
1. Press the O Key for at least three seconds to move from the operation
level to the initial setting level.
2. Select the Move to Advanced Function Setting Level parameter by press-
ing the M Key. (For details on moving between levels, refer to 4-8 Moving
to the Advanced Function Setting Level.)
3. Press the D Key to enter the password ( 169) and move from the initial
setting level to the advanced function setting level.
4. Press the M Key to select the Alarm 1 ON Delay parameter.
5. Press the U Key to set the parameter to 5.
6. Press the M Key to select the Alarm 1 OFF Delay parameter.
7. Press the U Key to set the parameter to 10.
8. Press the O Key for at least one second to move from the advanced
function setting level to the initial setting level.
Section 4-11
117