Advanced Function Setting Level
alsp
Alarm SP Selection
Function
Setting
See
See
manl
Manual MV Limit Enable
Function
Setting
See
See
244
This parameter sets whether the set point that triggers a deviation alarm dur-
ing SP ramp operation is to be the ramp SP or target SP.
• Set whether the set point that triggers a deviation alarm is the ramp SP or
target SP.
Setting range
sp-m: Ramp SP, sp: SP
■ Related Parameters
SP ramp set value (adjustment level): Page 193
ST (initial setting level): Page 205
This parameter sets whether the MV Upper Limit and MV Lower Limit param-
eters are to be enabled for manual MV in manual mode.
on: Enabled, off: Disabled
■ Related Parameters
MV upper limit, MV lower limit (adjustment level): Page 193
Alarm 1, 2, and 3 functions must be
assigned.
The SP Ramp Set Value parameter
must not be set to OFF.
The ST parameter must be set to
OFF.
The alarm type must be set to 1, 2, 3,
4, 5, 6, or 7.
The control must be set to 2-PID
control.
Setting range
Section 5-8
Default
sp-m
Default
OFF