Attention:
• Go over
"Installation Guidelines" on page 137
• Turn off the server and peripheral devices and disconnect the power cords and all external cables (see
"Power off the server" on page
• If the server is installed in a rack, slide the server out on its rack slide rails to gain access to the top cover,
or remove the server from the rack.
Procedure
Step 1.
Make preparations for this task.
a.
If drives or fillers have been installed, remove them (see
b.
Remove the top cover (see
c.
Remove the PCIe bracket cage from Zone 2 next to the power supplies (see
PCIe riser cage" on page
d.
Disconnect the cables from the 7mm drive cage.
Step 2.
Remove the 7mm drive cage.
Figure 154. Removing the 7mm drive cage
Remove the two screws that secure the drive cage.
Slide the drive cage forward to remove it.
After this task is completed
• Install a replacement unit or a filler (
• If you are instructed to return the component or optional device, follow all packaging instructions, and use
any packaging materials for shipping that are supplied to you.
• If you plan to recycle the component:
1. Remove the three screws that secure the two drive backplanes to the drive cage.
to ensure that you work safely.
12).
"Remove the top cover" on page
255).
"Install the 7mm drive cage" on page
"Remove a 7mm drive" on page
240).
266).
.
Chapter 4
Hardware replacement procedures
263).
"Remove a 4U
265