Field Settings for Indoor Unit
The set temperature displayed on the remote controller remains the same even if the target
As soon as people are detected while the temperature is shifted, this control will be cancelled
1.3.6 Auxiliary Electric Heater ON/OFF Temperature
Note(s)
1. S value varies automatically based on the room temperature trend.
FXFQ-T, FXMQ-PB
Mode
11 (21)
FXFQ-AA, FXZQ-TA, FXZQ-TB, FXUQ-P, FXUQ-PA, FXEQ-P, FXSQ-TA, FXSQ-TB,
FXMQ-TB, FXMQ-TA, FXLQ-M, FXNQ-M, FXTQ-TA, FXTQ-TB
Mode
11 (21)
149
(°F)
87.8
86
84.2
82.4
80.6
78.8
69.8
68
66.2
64.4
62.2
temperature is shifted.
(reset).
Thermostat
ON
First Code No. Symbol
No.
Ton
1
Toff
First Code No. Symbol
No.
1
Ton
2
Toff
State of absence
(°C)
31
30
29
28
27
Cooling (at 28°C (82.4°F))
26
21
Heating (at 20°C (68°F))
20
19
18
17
30 (60)
60 (120)
Elapsed time of absence (min.)
The values in parentheses represent the time
when Second code No. is 02.
Set temperature
Toff + S (∗1)
Ton + S (∗1)
01
02
–4°C
–3.5°C
(–7.2°F)
(–6.3°F)
(–5.4°F)
–2°C
–1.5°C
(–3.6°F)
(–2.7°F)
(–1.8°F)
01
02
–4°C
–3.5°C
(–7.2°F)
(–6.3°F)
(–5.4°F)
–2°C
–1.5°C
(–3.6°F)
(–2.7°F)
(–1.8°F)
Detection
Thermostat
OFF
: Factory setting
Second Code No.
03
04
05
–3°C
–2.5°C
–2°C
(–4.5°F)
(–3.6°F)
–1°C
–0.5°C
0°C
(–0.9°F)
(0°F)
: Factory setting
Second Code No.
03
04
05
–3°C
–2.5°C
–2°C
(–4.5°F)
(–3.6°F)
–1°C
–0.5°C
0°C
(–0.9°F)
(0°F)
Part 5 Field Settings and Test Operation
SiUS342004EB
06
–1.5°C
(–2.7°F)
0.5°C
(0.9°F)
06
–1.5°C
(–2.7°F)
0.5°C
(0.9°F)