Troubleshooting by Error Code
247
A
The relay cable has no
continuity.
NO
When
the airflow
direction flap-cam
mechanism is disconnected
from the swing motor, operation
is normal when turned
ON again.
YES
Model
1: Swing motor connector
FXHQ-M
X6A
FXAQ-P
X36A
YES
NO
2: Swing motor
M1S
M1S
SiUS342004EB
Replace the power supply
relay cable.
Replace the defective swing
motor. (∗2)
Take the flap-cam mechanism
apart, reassemble and turn ON
again.
Part 6 Service Diagnosis