Daikin VRV RXYQ72-384XAYCA Service Manual page 186

Heat pump 60 hz
Table of Contents

Advertisement

Field Settings for Outdoor Unit
No.
Item
1
Outdoor > 40 m
To increase Tc target heating.
(130 ft) below
35
indoor
Heat pump
Used for heat pump lockout
lockout 2
37
Emergency
To prohibit a compressor or
operation
complete in "Master". Since
38
(master)
module is permanent disabled,
immediately replace the defective
component(s).
Emergency
To prohibit a compressor or
operation (slave
complete "Slave 1". Since module
39
1)
is permanent disabled, immediately
replace the defective
component(s).
Emergency
To prohibit a compressor or
operation (slave
complete "Slave 2". Since module
40
2)
is permanent disabled, immediately
replace the defective
component(s).
Outdoor fan
Outdoor fan noise countermeasure
42
(limit fan speed).
Outdoor > 50 m
Height difference setting max. 90 m
49
(164 ft) above
(295 ft).
indoor
Sequence multi
Sequence addressing between
outdoor
master and slave units.
51
Gas furnace
Used for gas furnace connection
60
setting
Cooling/Heating
Adjust cooling and heating capacity
capacity learning
learning control
62
control
Phased
Used to make setting for phased
installation
installation.
64
setting
Heat pump
Heat pump is locked out when the
lockout
outdoor air temperature is smaller
temperature
than the heat pump lockout
temperature.
78
179
Description
SEG
1
2.
2.
2.
2.
2.
2.
2.
2.
2.
2.
2.
2.
7 segment
display
Description
SEG
SEG
2
3
Level > 40 m (130 ft)
Level max. 40 m (130 ft)
3
5
Do not use
OFF
Mode 1
Mode 2
3
7
Mode 3
Mode 4
Mode 5
Mode 6
OFF
Master unit OFF
3
8
OFF
Slave 1 unit OFF
3
9
OFF
Slave 2 unit OFF
4
0
Standard
4
2
Mode A
Mode B
Off (max. 50 m (164 ft))
4
9
On (max 90 m (295 ft))
Automatic
Forced master
5
1
Forced slave 1
Forced slave 2
No gas furnace connection
6
0
Gas furnace connection
OFF
Cooling adjustment
6
2
Heating adjustment
Cooling and heating
adjustment
OFF
Single module to dual module
6
4
installation
Dual module to triple module
installation
–26.1°C (–15°F)
–23.3°C (–10°F)
–20.5°C (–5°F)
–17.7°C (0°F)
–15°C (5°F)
–12.2°C (10°F)
–9.4°C (15°F)
7
8
–6.6°C (20°F)
–3.8°C (25°F)
–1.1°C (30°F)
1.6°C (35°F)
4.4°C (40°F)
7.2°C (45°F)
10°C (50°F)
Forced heat pump lockout
Part 5 Field Settings and Test Operation
SiUS342004EB
7 segment
display
Range
SEG
SEG
SEG
1
2
3
0
1
~
7
0
1
2
3
4
5
6
0
3
0
3
0
3
0
1
2
0
1
0
1
2
3
0
1
0
1
2
3
0
1
2
0
1
2
3
4
5
6
7
8
9
1
0
1
1
1
2
1
3
1
4