Daikin VRV RXYQ72-384XAYCA Service Manual page 77

Heat pump 60 hz
Table of Contents

Advertisement

SiUS342004EB
5. Press INSPECTION/TEST button for 1 second to return to normal mode.
Multiple Settings A/b
The command such as operation mode or temperature setting by this remote controller will be
rejected when the target indoor unit operation is restricted as by an external control such as
centralized control.
Since the setting acceptance is hard to discriminate with such circumstances there are two setting
options provided to enable discriminating by a beeping sound according to the operation:
A: Standard or b: Multi System. Set the setting according to the customer's intention.
Remote Controller
Multiple setting
Display on remote
controller
A: Standard
All items displayed.
(factory set)
b: Multi
Display only items
System
transmitted for a while.
Part 3 Remote Controller
Field setting mode
Address
Multiple setting
Indoor Unit
Behavior to the remote controller operation when
the functions are restricted as by an external
control.
Accepts the functions except restricted.
(Sounds one long beep or three short beeps)
There may be a difference from the indoor unit
status with remote controller display.
When some restricted functions are included in
the transmitted items
Accepts the functions except restricted.
(Sounds one long beep or three short beeps)
There may be a difference from the indoor unit
status with remote controller display.
When no restricted function is included
Accepts all items transmitted
(Sounds two short beeps)
The remote controller display agrees with the
indoor unit status.
Address Setting for Wireless Remote Controller
UP button
DOWN button
FAN button
RESERVE button
FILTER SIGN RESET button
INSPECTION/TEST button
Other than the left
Accepts all items transmitted (Sounds
two short beeps)
The remote controller display agrees
with the indoor unit status.
70

Advertisement

Table of Contents
loading

This manual is also suitable for:

Vrv rxyq72-384xbyca

Table of Contents