SiUS342004EB
Thermistor temperature
(°C)
(°F)
–30
–22
–25
–13
–20
–4
–15
5
–10
14
–5
23
0
32
5
41
10
50
15
59
20
68
25
77
30
86
35
95
40
104
45
113
50
122
55
131
60
140
65
149
70
158
75
167
80
176
85
185
90
194
95
203
100
212
105
221
110
230
115
239
120
248
125
257
130
266
135
275
140
284
145
293
150
302
Drawing No.
Part 6 Service Diagnosis
Type E
357.9
263.5
196.1
147.4
111.8
85.53
66.00
51.31
40.20
31.74
25.23
20.19
16.26
13.17
10.74
8.806
7.260
6.014
5.008
4.191
3.525
2.978
2.527
2.153
1.843
1.583
1.365
1.181
3S480025
(AD180054)
Resistance (k)
Type H
3407
2540
1910
1449
1108
853.8
662.7
517.9
407.4
322.5
256.9
205.7
165.7
134.3
109.4
89.58
73.73
60.98
50.67
42.29
35.45
29.84
25.21
21.38
18.21
15.57
13.36
11.49
9.92
8.594
7.465
6.499
5.675
4.968
4.360
3.836
3.384
3SA48006
(AD190115)
This data is for reference purposes only.
Check
Type J
352.1
261.2
195.4
147.3
111.8
85.49
65.80
51.15
40.08
31.64
25.16
20.14
16.23
13.16
10.73
8.800
7.255
6.012
5.010
4.196
3.532
2.987
2.538
2.166
1.857
1.598
1.380
1.196
1.041
0.908
0.795
0.698
0.615
0.543
0.481
0.428
0.381
3SA48005
(AD190114)
368