Blower Motor Communication Error - Daikin VRV RXYQ72-384XAYCA Service Manual

Heat pump 60 hz
Table of Contents

Advertisement

Troubleshooting by Error Code

3.21 Blower Motor Communication Error

Applicable
FXTQ-TA, FXTQ-TB
Models
C1-07
Error Code
Outline
Error is issued if transmission abnormalities occur between indoor unit and fan motor.
Error Decision
If the response message from the fan motor is an abnormal message, and determined as such by
Conditions
the indoor unit, the indoor unit will execute a retry.
If everything fails for 5 seconds, it is deemed to be a transmission abnormality.
Error Reset
If the indoor unit receives even a single normal response message from the fan motor, the error will
Conditions
be cleared.
Supposed
 Incorrect or loose wiring
Causes
 Power interruption (low voltage)
Corrective
 Check wiring or tighten wiring connections if needed.
Actions
 Verify the input voltage at the motor.
 Replace the indoor unit PCB or motor.
267
SiUS342004EB
Part 6 Service Diagnosis

Advertisement

Table of Contents
loading

This manual is also suitable for:

Vrv rxyq72-384xbyca

Table of Contents