SiUS342004EB
1.3.21 Airflow Setting when Cooling Thermostat is OFF
This is used to set airflow to LL airflow when cooling thermostat is OFF.
If the airflow setting when thermostat is OFF is set to 03: OFF, the air in the indoor unit will be
stagnant and suction air thermistor may not detect room temperature correctly, resulting in
problems that thermostat will not be ON easily.
Use optional remote sensor in such conditions, or set the field setting 10 (20)-2 to 03 (only remote
controller thermistor).
Mode
12 (22)
1.3.22 Ceiling Height Setting, Setting of Normal Airflow
Make the following setting according to the ceiling height. The second code No. is set to 01 at the
factory.
FXFQ07-24AA, FXFQ07-24T
Mode
No.
(23)
Note(s)
1. The Second Code No. is factory set to Standard/All round outlet. For High ceiling (1) or (2),
2. A closing member kit (optional) is required for 4-, 3-, or 2-direction airflow.
FXFQ30-54AA, FXFQ30-48T
Mode
No.
(23)
Note(s)
1. The Second Code No. is factory set to Standard/All round outlet. For High ceiling (1) or (2),
2. A closing member kit (optional) is required for 4-, 3-, or 2-direction airflow.
Part 5 Field Settings and Test Operation
First Code
Second Code
No.
No.
No.
01
02
6
03
First
Second
Code
Setting
Code No.
No.
Standard
01
13
0
02
Ceiling (1)
03
Ceiling (2)
initial setting by remote controller is required.
First
Second
Code
Setting
Code No.
No.
Standard
01
13
0
02
Ceiling (1)
03
Ceiling (2)
initial setting by remote controller is required.
All round outlet
4-way outlets
Lower than
Lower than
2.7 m
(8-3/4 ft)
Lower than
High
3.0 m
(10 ft)
Lower than
High
3.5 m
(11-1/2 ft)
All round outlet
4-way outlets
Lower than
Lower than
3.2 m
(10-1/2 ft)
Lower than
High
3.6 m
(12 ft)
Lower than
High
4.2 m
(13-3/4 ft)
Field Settings for Indoor Unit
: Factory setting
Contents
LL tap
Set fan speed
OFF
: Factory setting
Ceiling Height
3-way outlets
Lower than
3.1 m
3.0 m
(10-1/8 ft)
(10 ft)
Lower than
Lower than
3.4 m
3.3 m
(11-1/8 ft)
(10-3/4 ft)
Lower than
Lower than
4.0 m
3.5 m
(13-1/8 ft)
(11-1/2 ft)
: Factory setting
Ceiling Height
3-way outlets
Lower than
3.4 m
3.6 m
(11-1/8 ft)
(12 ft)
Lower than
Lower than
3.9 m
4.0 m
(12-3/4 ft)
(13-1/8 ft)
Lower than
Lower than
4.5 m
4.2 m
(14-3/4 ft)
(13-3/4 ft)
2-way outlets
Lower than
3.5 m
(11-1/2 ft)
Lower than
3.8 m
(12-1/2 ft)
2-way outlets
Lower than
4.2 m
(13-3/4 ft)
Lower than
4.2 m
(13-3/4 ft)
156