9.11 Heater Control (Except FXTQ-TA, FXTQ-TB Models)

Note(s)
Optional PCB KRP1B... is required.
The heater control is conducted in the following manner.
Normal control
While in heating, the heater control (ON/OFF) is conducted as shown below.
Overload control
When the system is overloaded in heating, the heater will be turned OFF in the following 2
manners.
1. The heater control (ON/OFF) is conducted through the liquid pipe temperature (R2T) of the
2. The heater control (ON/OFF) is conducted by converting the heater temperature into the
Fan residual
While the heater turns OFF, in order to prevent the activation of the thermal protector, the fan
operation
conducts residual operation for a given period of time after the heater turns OFF. (This operation is
conducted regardless of with or without heater equipped.)
Residual operation time: 100 seconds on ceiling suspended type or 60 seconds on other types
Part 4 Functions and Control
ON
indoor unit.
ON
condensing pressure equivalent saturated temperature (Tc) according to the temperature
detection through the high pressure sensor (S1NPH) of the outdoor unit.
ON
50˚C (122˚F)
Set temperature
2˚C
2˚C
(3.6˚F)
(3.6˚F)
43˚C (109.4˚F)
50˚C (122˚F)
60˚C (140˚F)
Outline of Control (Indoor Unit)
OFF
Liquid pipe temperature
OFF
Condensing pressure
equivalent saturated
temperature
OFF
124