Daikin VRV RXYQ72-384XAYCA Service Manual page 185

Heat pump 60 hz
Table of Contents

Advertisement

SiUS342004EB
No.
Item
1
Power transistor
Used to troubleshoot DC
check
compressor. Inverter waveforms
are output without wire connections
28
to the compressor. It is useful to
determine whether the relevant
trouble has resulted from the
compressor or inverter PCB.
Capacity priority
Cancel the low noise level control if
setting
capacity is required while low noise
29
operation or night-time low noise
operation is in progress.
Demand 1
Used to make a change to the
setting
targeted power consumption level
when the demand 1 control signal
is inputted.
30
Demand 2
Used to use a targeted power
31
setting
current level when the demand 2
control signal is input.
Normal demand
Used to set permanent demand 1
32
setting
or 2 control without inputting any
external signal.
Indoor fan tap
Indoor fan speed is limited to L tap
setting
depending on connection capacity
and outdoor air temperature (Ta).
Indoor condition A: Temperature
difference average of (indoor air
temperature – set temperature) is
less than 1.5°C (2.7°F).
Indoor condition B: Temperature
difference average of (indoor air
temperature – set temperature) is
3°C (5.4°F) or more.
34
Part 5 Field Settings and Test Operation
Description
SEG
1
2.
2.
2.
2.
2.
2.
7 segment
display
Description
SEG
SEG
2
3
OFF
ON (10 Hz)
2
8
OFF
ON
2
9
Level 1 (60%)
Level 2 (65%)
Level 3 (70%)
Level 4 (75%)
3
0
Level 5 (80%)
Level 6 (85%)
Level 7 (90%)
Level 8 (95%)
Level 1 (40%)
3
1
Level 2 (50%)
Level 3 (55%)
OFF
3
2
Demand 1 (2-30)
Demand 2 (2-31)
Indoor capacity ≥ 130%
Indoor capacity ≥ 130% in
heating
Remote controller setting (Not
limited)
Limited in cooling when
Ta < 29.5°C (85.1°F) and
Indoor condition is in condition
A (1)
Returned when
Ta > 32.5°C (90.5°F) or Indoor
condition is in condition B (2)
Limited in cooling when
Ta < 23.5°C (74.3°F) and
Indoor condition is in condition
A (1)
Returned when
Ta > 26.5°C (79.7°F) or Indoor
condition is in condition B (2)
3
4
Limited in cooling when
Ta < 19.3°C (66.7°F) and
Indoor condition is in condition
A (1)
Returned when
Ta > 22.3°C (72.1°F) or Indoor
condition is in condition B (2)
Limited in cooling when
Ta < 29.5°C (85.1°F)
Returned when
Ta > 32.5°C (90.5°F)
Limited in cooling when
Ta < 23.5°C (74.3°F)
Returned when
Ta > 26.5°C (79.7°F)
Limited in cooling when
Ta < 19.3°C (66.7°F)
Returned when
Ta > 22.3°C (72.1°F)
Field Settings for Outdoor Unit
7 segment
display
Range
SEG
SEG
1
2
SEG
3
0
1
0
1
1
2
3
4
5
6
7
8
1
2
3
0
1
2
0
1
2
3
4
5
6
7
8
178